Appeal 7368
Appeal Summary
Status: Decision rendered
Appeal ID: 7368
Submission Date: 9/19/10 10:01 PM
Hearing Date: 9/22/10
Case #: B-009
Appeal Type: Building
Project Type: commercial
Building/Business Name: IDL Worldwide
Appeal Involves: Alteration of an existing structure
Proposed use: Office Space
Project Address: 135 NW Park Ave
Appellant Name: Jason Siemer
LUR or Permit Application #: Permit 10-173569-10
Stories: 2 Occupancy: Business Group B Construction Type: Tenant Improvement
Fire Sprinklers: No
Plans Examiner/Inspector: David Jones
Plan Submitted Option: pdf [File 1] [File 2] [File 3]
Payment Option: mail
Appeal Information Sheet
Appeal item 1
| Code Section | Section 301.1, Chapter 34 – Structural Specialty Code |
|---|---|
| Requires | Existing Group B assembly occupancies with an occupant load of 50 or more may be
Division 2 requirements;
to more than 100 persons including staff and customers;
required design loads for Group A, Division 2 occupancy;
of the OSSC. In addition, the path of travel to altered areas must be improved to
B occupancy and shall include a seating layout noting the number of occupants |
| Code Modification or Alternate Requested | |
| Proposed Design | We are not proposing any significant design changes. We would like for the appeals board to reconsider the decision of the plans reviewer to classify the open area of the first floor of the office as A3 occupancy. We are providing plans from 2001 illustrating that the previous tenant was granted a building permit and class B occupancy. We are also providing current plans which illustrate that we are not making significant changes in layout or usage. We are providing a letter from the company primary explaining in detail how we intend to occupy the same space. |
| Reason for alternative | No alternative suggested. Please see proposed egress lighting plan and occupancy matrices. |
Appeal Decision
1. Number of occupants and Group B Occupancy classification: Granted as proposed for this tenant and configuration only.
Note: Assembly events exceeding 49 total occupants on the ground floor shall require a Temporary Public Assembly Permit for Non-Assembly Type Occupancies Event Permit issued by the Fire Marshal's Office. Appellant may contact Kim Kosmas (503-823-3835) for more information about assembly permits.