Appeal 10222

Appeal Summary

Status: Decision Rendered

Appeal ID: 10222

Submission Date: 10/27/13 2:50 PM

Hearing Date: 10/30/13

Case #: B-011

Appeal Type: Building

Project Type: commercial

Building/Business Name: Portland Tennis Center

Appeal Involves: Erection of a new structure

Proposed use: Covered Tennis Court

Project Address: 324 NE 12th Ave

Appellant Name: Samir Mokashi

LUR or Permit Application #: Preliminary

Stories: 1 Occupancy: A-4 Construction Type: II-B

Fire Sprinklers: No

Plans Examiner/Inspector: .

Plan Submitted Option: pdf   [File 1]   [File 2]

Payment Option:

Appeal Information Sheet

Appeal item 1

Code Section

1004.1.1 Areas without fixed seating

Requires

The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.1. For areas without fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant per unit of area factor assigned to the occupancy as set forth in Table 1004.1.1. Where an intended use is not listed in Table 1004.1.1, the building official shall establish a use based on a listed use that most nearly resembles the intended use.

Exception: Where approved by the building official, the actual number of occupants for whom each occupied space, floor or building is designed, although less than those determined by calculation, shall be permitted to be used in the determination of the design occupant load.

Code Modification or Alternate Requested
Proposed Design

The proposed design meets the requirement of OSSC §1004.1.1 exception. The occupant load of the space will be posted to not exceed 250 occupants.

The expected maximum number of occupants is 132.

The protection measures provided will be:

  1. Supervision of space and occupants to maintain maximum occupant load.
  2. Permanent signs of an approved size and legibility indicating Maximum Occupant Load conspicuously posted at the entry doorway per OSSC 1004.3.
  3. Provide means of egress illumination, equipped with emergency power per OSSC.
  4. Provide illuminated exit signage, equipped with emergency power per OSSC.
  5. Tennis courts will be free of partitions and maintain a clear view of the entry/exit door.
Reason for alternative

The building will be a 25,300 sq. ft. domed inflatable building installed over four existing tennis courts owned by Portland Parks and Recreation. There are two sets of existing bleachers located in the middle of the courts. Two exits with 4 foot doors and equipped with panic hardware will be installed.

The facility provides indoor tennis courts for year round use. The use of the tennis courts will be monitored and administered through city staff. The courts are reserved by paid members or by the public for a paid fee on a walk-in basis. The tennis courts will not be used for any other use other than its intended purpose. Portland Parks and Recreation has alternate facilities for the purposes of banquets, classes, and other assembly uses. They will regulate use of this space

Monitored by city staff the highest occupancy of the tennis courts will be 132 occupants during tournaments. This accounts for a doubles game in each court, with 4 ball boys and referees per court, and both sets of bleachers filled to capacity. Per §1004.7, using 18” per occupant, each of the two bleachers will hold 50 occupants.

The tennis facility is a large open space with no partitions within the building that will hinder visibility or egress from the space. It will have two means of egress that will be clearly visible from all portions building that exit directly to the exterior with easy access to a public right of way.

Due to the restricted, monitored use of the tennis courts, familiarity with the facility by the members using it, and the clear and visible access to the exits, the proposed occupancy limit of 250 persons is appropriate for the facility and will provide adequate protection for the occupants, therefore we request approval.

Appeal item 2

Code Section

101.5 Compliance

Requires

101.5 Compliance. Residential buildings shall meet the provisions of Chapter 4. Commercial buildings shall meet the provisions of Chapter 5.
101.5.1 Low energy buildings. The following buildings, or portions thereof, separated from the remainder of the building by building thermal envelope assemblies complying with this code shall be exempt from the building thermal envelope provisions of this code:

  1. Those with a peak design rate of energy usage less than 3.4 Btu/h • ft2 (10.7 W/m2) or 1.0 watt/ft2 (10.7 W/m2) of floor area for space conditioning purposes.
  2. Those that do not contain conditioned space.
Code Modification or Alternate Requested
Proposed Design

The proposed design will be a 25,300 sq. ft. domed inflatable building installed over four existing tennis courts owned by Portland Parks and Recreation. We propose that the building be considered an unconditioned space and is therefore exempt from the requirements for compliance with the 2010 Oregon Energy Efficiency Specialty Code (OEESC).
The proposed design for energy efficiency will have the following elements:

• The building will only be heated during the winter months to a temperature of 50 ºF.
• The heating unit will be placed on an automatic timer and will be operated during the hours of operation between 6pm and 11pm.
• The inflatable membrane will be triple walled and will have an R-value of 4.4.

Reason for alternative

It is impractical for an inflatable structure to satisfy the requirements of the 2010 OEESC. This can be seen in that some states, such as Vermont who exempt inflatable structures from having to comply with the Energy Efficiency Code.

The structure will be occupied and potentially heated from 6pm –11pm each evening. The building will only be heated during the winter months to a temperature of no more than 50 ºF. Based upon temperature data provided by NOAA, the building will be heated less than 5% of the time.
Portland Parks and Recreation is choosing to be energy efficient by having purchased a building with a triple wall membrane with an R-value of 4.4 and limiting heating to 50 ºF. The building will use significantly less energy than the comparable tennis facility of construction type IIIB immediately adjacent.

Appeal Decision

1. Alternate occupant load for covered tennis courts: Granted as proposed.

AMENDED 5/7/14 per appeal ID 10707: Posted occupant load is limited to 120 occupants.

2. Heating set point and alternate energy envelope: Denied. Proposal does not provide equivalent energy conservation compliance. Appellant may contact Marcia Karr (503-823-1107) for more information.

The Administrative Appeal Board finds that the information submitted by the appellant demonstrates that the approved modifications or alternate methods are consistent with the intent of the code; do not lessen health, safety, accessibility, life, fire safety or structural requirements; and that special conditions unique to this project make strict application of those code sections impractical.