Appeal 10831

Appeal Summary

Status: Decision Rendered

Appeal ID: 10831

Submission Date: 6/11/14 5:04 PM

Hearing Date: 6/18/14

Case #: P-003

Appeal Type: Plumbing

Project Type: lur

Building/Business Name: Lance Johnson owner

Appeal Involves: Erection of a new structure

Proposed use: Residential

Project Address: 5920 SW 18th Dr, Lot 7

Appellant Name: Lance Johnson

LUR or Permit Application #: LUR 13-170739-LU

Stories: 2 Occupancy: Residential Construction Type: Residential

Fire Sprinklers: No

Plans Examiner/Inspector: Kate Greene, Jim Jones, Janell Piercy, Tim Morris

Plan Submitted Option: pdf   [File 1]   [File 2]

Payment Option: mail

Appeal Information Sheet

Appeal item 1

Code Section

709.0

Requires

Oregon Specialty Plumbing Code
709.0 Requires that "Wherever practicable, plumbing fixtures shall be drained to public sewers . . by gravity."

As part of our application for a Land Division Amendment (LU13-170739), our planner has requested that we request this plumbing code appeal to pump sanitary for lots 7 -9 and provide the appeal results.

Code Modification or Alternate Requested
Proposed Design

We propose to install private sanitary pump systems in the most eastern and lowest three lots (lot 7, lot 8, and lot 9). The private sanitary pump stations would meet appropriate city codes and would be approved through future building permit process.

Reason for alternative

The private sanitary pump systems - as alternates to gravity drainage systems - are required because public sanitary sewer service is not available at an elevation to serve the lower three lots. The systems would be designed with appropriate controls and fail safe measures per code to provide equivalent health, accessibility, structural capacity, life safety, and fire protection as a code built system. Electrical service and controls of the pump stations would meet and/or exceed appropriate electrical codes. Pump and pipe capacity would be designed to meet and/or exceed appropriate mechanical codes.

Appeal Decision

Private sanitary pump system in lieu of gravity system: Granted provided that any fixtures in the dwelling that can achieve gravity drainage shall be made to comply with 709.0 and 710.1. Other fixtures may utilize 710.2 thru 710.10 in conjunction with proposed design.

The Administrative Appeal Board finds that the information submitted by the appellant demonstrates that the approved modifications or alternate methods are consistent with the intent of the code; do not lessen health, safety, accessibility, life, fire safety or structural requirements; and that special conditions unique to this project make strict application of those code sections impractical.