Appeal 11327
Appeal Summary
Status: Decision Rendered
Appeal ID: 11327
Submission Date: 11/17/14 10:47 AM
Hearing Date: 11/19/14
Case #: M-002
Appeal Type: Building
Project Type: commercial
Building/Business Name: Maranatha Church
Appeal Involves: Addition to an existing structure
Proposed use: church
Project Address: 4222 NE 12th Ave
Appellant Name: Jermaine Atherton
LUR or Permit Application #: Preliminary
Stories: 2 Occupancy: Not given Construction Type: Kitchen
Fire Sprinklers: Yes - Throughout building
Plans Examiner/Inspector: Marcia Karr
Plan Submitted Option: mail [File 1]
Payment Option: mail
Appeal Information Sheet
Appeal item 1
Code Section | 507.2.3 |
---|---|
Requires | A single domestic cooking appliance installed where domestic cooking operations occur, such as a church... shall meet the requirements of Section 505.1. IMC 505.1 requires a ducted |
Code Modification or Alternate Requested | |
Proposed Design | The proposed design is to allow for two ranges instead of just one at the church. Both ranges |
Reason for alternative | The church will not serve the public. The ranges will only be used for special events at the |
Appeal Decision
Installation of residential range hood over domestic cooking appliances: Granted as proposed.
The Administrative Appeal Board finds that the information submitted by the appellant demonstrates that the approved modifications or alternate methods are consistent with the intent of the code; do not lessen health, safety, accessibility, life, fire safety or structural requirements; and that special conditions unique to this project make strict application of those code sections impractical.