Appeal 12114
Appeal Summary
Status: Decision Rendered
Appeal ID: 12114
Submission Date: 6/12/15 5:01 PM
Hearing Date: 6/17/15
Case #: B-011
Appeal Type: Building
Project Type: commercial
Building/Business Name:
Appeal Involves: Erection of a new structure
Proposed use: 14-story residential tower with ground floor retail and matrix parking
Project Address: 535 NW 11th Ave
Appellant Name: Samir Mokashi
LUR or Permit Application #: LUR 15-169591-LU
Stories: 14 Occupancy: A-3, M, R-2, S Construction Type: I-A
Fire Sprinklers: Yes - Throughout
Plans Examiner/Inspector: Jerry Engelhardt
Plan Submitted Option: pdf [File 1] [File 2] [File 3] [File 4]
Payment Option: electronic
Appeal Information Sheet
Appeal item 1
| Code Section | OSSC 3007.7 |
|---|---|
| Requires | 3007.7 Fire service access elevator lobby. The fire service access elevator shall open into a fire service access elevator lobby in accordance with Sections 3007.7.1 through 3007.7.5. Exception: Where a fire service access elevator has two entrances onto a floor, the second entrance shall be permitted to open into an elevator lobby in accordance with Section 708.14.1. 3007.7.1 Access. The fire service access elevator lobby shall have direct access to an enclosure for an interior exit stairway. 3007.7.2 Lobby enclosure. The fire service access elevator lobby shall be enclosed with a smoke barrier having a fire-resistance rating of not less than 1 hour, except that lobby doorways shall comply with Section 3007.7.3. Exception: Enclosed fire service access elevator lobbies are not required at the levels of exit discharge. 3007.7.3 Lobby doorways. Other than the door to the hoistway, each doorway to a fire service access elevator lobby shall be provided with a 3/4-hour fire door assembly complying with Section 716.5. The fire door assembly shall also comply with the smoke and draft control door assembly requirements of Section 716.5.3.1 with the UL 1784 test conducted without the artificial bottom seal. 3007.7.4 Lobby size. Each enclosed fire service access elevator lobby shall be a minimum of 150 square feet (14 m2) in an area with a minimum dimension of 8 feet (2440 mm). 3007.7.5 Fire service access elevator symbol. A pictorial symbol of a standardized design designating which elevators are fire service access elevators shall be installed on each side of the hoistway door frame on the portion of the frame at right angles to the fire service access elevator lobby. The fire service access elevator symbol shall be designed as shown in Figure 3007.7.5 and shall comply with the following:
|
| Code Modification or Alternate Requested | |
| Proposed Design | The proposed building design will meet all the requirements for a Fire Service Access Elevator lobby except that the lobby will be the entire corridor on each floor. Equivalent protection for the lobby will be provided by the following (see drawing):
Additional protection in the corridors will be provided by: A. Automatic smoke detectors will be provided along the entire length of the rated corridor. Elevator shafts shall be pressurized against smoke migration in accordance with §909.21. |
| Reason for alternative | The building is of Type IA construction with non-separated A-3, M, S-2 and R-2 occupancy groups. The corridor on all levels except the level of discharge will be separated from all other areas by 1 hour fire barriers with 45 minute rated doors per OSSC 716.5.3.1. The proposed design for the fire service access elevator opening into the corridor is based on the exception provided by the City of Seattle, except the corridor will be used for the fire service access elevator lobby on all levels including the basement and parking levels. Compartmentalization will be provided on all levels in this small footprint building, by required separation between dwelling units and one-hour separation between storage rooms in the basement level. Smoke detectors along the entire length of the corridor will provide additional time for occupants to respond to a fire event and begin to egress. City of Seattle exempts fire service access elevator lobby from the IBC-based lobby requirements on High-Rise Buildings for residential floors. This exception has gone through an independent rational analysis and approval process. The rational analysis is based on the compartmentalization required for residential units, which reduces the impacts of a fire/smoke event on the corridor, and pressurization of stair and elevator shafts. The compartmentalization and pressurization limits smoke migration and impact on the corridor. Seattle has more high rise buildings than Portland and is the basis for this proposal. This proposal exceeds the requirements of the Seattle exceptions (included here). Exceptions:
The pressurization will follow the requirements of OSSC 909.21, which has higher performance requirements than those required by the City of Seattle. OSSC requires the specified pressure differential across all floors, rather than just 4 floors as permitted by Seattle. Since all elevators and stairs are pressurized, smoke migration between floors has been addressed. If the lobbies were fully enclosed, additional doors would reduce the available area and hinder rather than help firefighting efforts. The cumulative effect of the increased area of protection, added smoke detection, and the shaft pressurization backed up by the analysis performed on the Seattle exception, we believe meets the code intent for protection of firefighting operations on each floor, and we therefore request approval of this proposed design. |
Appeal item 2
| Code Section | OSSC 1008.1.9.9 |
|---|---|
| Requires | 1008.1.9.9 Electromagnetically locked egress doors. Doors in the means of egress in buildings with an occupancy in Group A, B, E, M, R-1 or R-2, and doors to tenant spaces in Group A, B, E, M, R-1 or R-2, shall be permitted to be electromagnetically locked if equipped with listed hardware that incorporates a built-in switch and meet the requirements below:
|
| Code Modification or Alternate Requested | |
| Proposed Design | This proposed residential building design includes a parking garage where we propose to use an Electromagnetically Locked Egress Door, serving as one of the required exit access doors from the Level 1 parking area (S-2 occupancy) into the main building lobby (R-2 occupancy). Although an electronically locked egress door is permitted as an egress door in an R2 occupancy, the door is serving the S2 parking garage. The following mitigating measures are proposed:
|
| Reason for alternative | The parking garage is restricted use and only the building residents have access to it. The main reason for the controlled access is to ensure that no one other that a resident can enter the main building lobby. This is essentially to maintain a secure environment for all the tenants. The code allows for an Electronically Locked Egress Door in Group A, B, E, M, R-1 or R-2 uses. Although the parking garage is classified as S2 occupancy it is serving the R2 occupancy, which is the primary occupancy of this building. All occupants of the parking area will be intimate with the building and will use building provided fobs for accessing the lobby from the S-2 parking area. In case of a power failure the door will unlock and occupants will be able to exit the area without the need to use fobs. |
Appeal item 3
| Code Section | OSSC 403.3.2 |
|---|---|
| Requires | 403.3.2 Water supply to required fire pumps. Required fire pumps shall be supplied by connections to no fewer than two water mains located in different streets. Separate supply piping shall be provided between each connection to the water main and the pumps. Each connection and the supply piping between the connection and the pumps shall be sized to supply the flow and pressure requirement for the pumps to operate. Exception: Two connections to the same main shall be permitted provided the main is valved such that an interruption can be isolated so that the water supply will continue without interruption through no fewer than one of the connections. |
| Code Modification or Alternate Requested | |
| Proposed Design | This project is a 14-story (149 feet) residential high-rise. The proposed design is an on-site fire water reservoir supplied by a single connection to the water main in NW Hoyt. A 6 inch fire service water line is to be installed by City of Portland water bureau under separate permit. The fire pump will be supplied from the fire water reservoir. The tank is sized in accordance with the Portland Fire Design Manual and 11.2.3.1.1 of NFPA 13 and the connection will be designed to refill the tank at a rate of at least equal to the most demanding sprinkler or standpipe design requirements, including hose allowances, per the Portland Fire Design Manual. Tank size: Duration is 60 minutes per Portland Design Guidelines = 42,000 gallons. Standpipe design is 500 gallons per minute at most remote standpipe plus 250 gallons per minute at all additional required standpipes = 750 gallons per minute. Duration is 30 minutes per NFPA 13 and Portland Fire Design Manual = 22,500 gallons. Tank to be sized to accommodate a minimum 42,000 gallons. Tank refill rate to be a minimum of 750 gallons per minute. 1,300 gallons per minute is available at NW Hoyt per flow simulation ID 2177. |
| Reason for alternative | The fire pump takes its supply from the fire water tank. The tank is sized to accommodate the largest of the sprinkler system or standpipe demand for the duration specified in NFPA 13 and/or Portland Fire Design Manual. The tank is automatically refilled at the maximum of the sprinkler system or standpipe requirements. This arrangement provides redundant water supplies via the city main (primary supply) and the fire water tank (secondary supply). Portland Fire has allowed a single-connection from the public water source, sized per the Portland Fire Design Manual, to provide sufficient redundancy to provide reasonable protection for buildings less than 420 feet in height. This proposal meets a similar intent as granted in past appeals. |
Appeal item 4
| Code Section | OSSC 713.13.1 and 713.13.3 |
|---|---|
| Requires | 713.13.1 Refuse, recycling and laundry chute enclosures. A shaft enclosure containing a refuse, recycling, or laundry chute shall not be used for any other purpose and shall be enclosed in accordance with Section 713.4. Openings into the shaft, including those from access rooms and termination rooms, shall be protected in accordance with this section and Section 716. Openings into chutes shall not be located in corridors. Doors shall be self- or automatic-closing upon the actuation of a smoke detector in accordance with Section 716.5.9.3, except that heat-activated closing devices shall be permitted between the shaft and the termination room. 713.13.3 Refuse, recycling and laundry chute access rooms. Access openings for refuse, recycling and laundry chutes shall be located in rooms or compartments enclosed by not less than 1-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. Openings into the access rooms shall be protected by opening protectives having a fire protection rating of not less than ¾ hour. Doors shall be self- or automatic-closing upon the detection of smoke in accordance with Section 716.5.9.3. |
| Code Modification or Alternate Requested | |
| Proposed Design | The proposed design meets the requirements of Section 713.13.3, except the space in front of the chute is not a room. The proposed design will provide: See Trash Chute Plan for more information. |
| Reason for alternative | The proposed design is requested due to space constraints within a building sited on a 1/4 block. Beyond the requirements within Section 713.13, the proposed design offers additional protection by providing a 2-hour fire-resistance-rated compartment in front of the chute, separating the chute from the fire-rated corridor at Levels 2 through 14. The intent of the code is satisfied by providing a rated enclosure in addition to the rated shaft. 8 inches of space within the compartment is provided to fit a sprinkler head. The delay on the automatic closer allows the door to stay open while the chute is being accessed without the user having to hold it open. This allows a disabled person time to deposit trash without having to at the same time hold the door open. This configuration is compliant with the 2009 A117.1, as room for a forward approach is provided. The proposed design provides equivalent protection by ensuring that separation is maintained between the corridor and the chute even if the trash chute door is stuck open and by providing the space necessary for a forward approach. By providing 2-hour fire-resistance-rated construction as described, the proposed design exceeds the code requirements and we request that the proposed design be approved. |
Appeal Decision
1. Corridor to Serve as Fire Service Access Elevator Lobby on Residential Floors: Granted as proposed.
2. Electro-magnetic Lock at Egress Door from Parking Garage: Granted provided a pull station is provided at the door and the electro-magnetic lock is tied into the fire alarm system such that activation of the fire alarm system will unlock this door. This appeal assumes that the only occupants using the parking garage are building residents.
3. One Water Supply to Required Fire Pumps: Granted in concept. The proposed capacity for the secondary on-site water supply as outlined in this appeal is not approved. Please contact Jim Hanson (503 823-2148) for more information.
4. Trash Chute Access Compartment at Corridor: Granted as proposed. Sprinkler to be installed under separate permit from the Fire Marshal's Office.
The Administrative Appeal Board finds that the information submitted by the appellant demonstrates that the approved modifications or alternate methods are consistent with the intent of the code; do not lessen health, safety, accessibility, life, fire safety or structural requirements; and that special conditions unique to this project make strict application of those code sections impractical.