Appeal 13911
Appeal Summary
Status: MIXED: Items 1-3: Decision Rendered, Item 4: Hold for additional information.
Appeal ID: 13911
Submission Date: 8/24/16 4:53 PM
Hearing Date: 8/31/16
Case #: B-018
Appeal Type: Building
Project Type: commercial
Building/Business Name: Towne Storage Building
Appeal Involves: Addition to an existing structure
Proposed use: B- Business / creative office
Project Address: 17 SE 3rd Ave
Appellant Name: Michael Roberts
LUR or Permit Application #: Permit 16-175526-CO
Stories: 6 Occupancy: B, A-2 Construction Type: III-A
Fire Sprinklers: Yes - Through out
Plans Examiner/Inspector: John Butler, Ericka Koss, Doug Morgan
Plan Submitted Option: pdf [File 1] [File 2] [File 3] [File 4] [File 5]
Payment Option: electronic
Appeal Information Sheet
Appeal item 1
| Code Section | Table 503 , 302.1 General |
|---|---|
| Requires | This specific appeal concerns the COP’s plan checksheet item #20 applying an A occupancy to the building's 6th floor roof deck(s) whereby the Table 503 states such an occupancy (A) at that story is not permitted. Based upon the written and attached analysis submitted by the Architect, this is a misapplication of the code. |
| Code Modification or Alternate Requested | |
| Proposed Design | West & East decks on Level 6 of building allowed. |
| Reason for alternative | Below are applicable OSSC Definitions (202) to consider in determining the building’s exterior roof deck requirements: Building: Any structure used or intended for supporting or sheltering any use or occupancy. Court: An open, uncovered space, unobstructed to the sky, bounded on three or more sides by exterior building walls or other enclosing devices. The relevant question is what parts of the code are applicable to the regulation of rooftop decks that are intended to be used by building occupants?
Conclusion: A rooftop deck intended for use by the building occupants should be classified with an occupancy classification since the there is a “use” of the roof and the roof is part of a “structure.”
Conclusion: A roof, irrelevant of whether it has a use or not, is not a story, since a story, as defined, has a roof or floor above. (A roof has no roof or story above.) So a roof with a deck “use” is not required to comply with the provisions of Chapter 5 and Table 503 for limiting the height or stories, in which the use on a roof occurs.
Conclusion: A roof, irrelevant of whether it has a use or not, is not part of a building area, since building area, as defined, has walls and/ or a roof above. So a roof with a deck use is not required to comply with the provisions of Chapter 5 and Table 503 for limiting the building area in which the use on a roof occurs.
Conclusion: A roof with a use is required to meet the construction type requirements of Chapter 6 for roofs and the structural loading requirements of Chapter 16 for roofs and the intended use.
Conclusion: A roof with a use is required to meet the applicable provisions for its intended use for Chapter 10 Means of Egress, Chapter 11 Accessibility, and Chapter 15 Roofing. It is also required to meet limited applicable provisions of Chapter 7 and 9. This code analysis concludes that placing a use on a roof (per 302.1) creates an occupancy classification for the use. That classification then properly requires rooftop uses to comply with means of egress, accessibility, structural and potentially limited other requirements such as detection requirements. This analysis also properly concludes that other aspects of the code (table 503) are not applicable. The code does not regulate story or height limitations in an open-air-non-story, non-building area, as defined, such as a rooftop deck use, because it is not within walls and is not under a structure. This is consistent with the code’s assumption of increased fire hazards only in confined spaces within and under something, not on a roof. Furthermore, the International Code Council reviewed multiple proposals and approved one proposal concerning rooftop uses for its 2018 IBC. The proposed change G24-15 PC#2 was Approved as Modified by Public Comment (AMPC) (Public Comment #2) in its Final Action for Group A proposed changes for the 2018 IBC with the addition of new section 503.1.4 Occupied roofs. The multiple proponents, consisting of various code specialists, joined together and created clarifications for rooftop uses. Their public comment reason statement drew the same code analysis conclusions of this submitted analysis. They also further regulated those uses only in non sprinklered buildings. 2018 IBC Commentary Attached (7 pages.) |
Appeal item 2
| Code Section | 403.4.6 Fire command and specifically: 911.1.3 size |
|---|---|
| Requires | The room shall be a minimum of 200 square feet with a minimum dimension of 10ft. |
| Code Modification or Alternate Requested | |
| Proposed Design | The new fire command center (FFC) footprint is configured so that a portion of the room is less than the 10 foot minimum. Overall the area of the FCC exceeds code at 205 square feet. Refer to attached Towne Storage floor plan. |
| Reason for alternative | This is an existing historic building under renovation where the geometry of this renovated building’s main floor lobby and elevator, the exiting column layout and the FFC’s door placement has created this layout. The 200 SF area requirement meets code. This a new renovated historic building with a new automatic sprinkler system for protection. |
Appeal item 3
| Code Section | PCC 24.50.050 & 24.50.06 OSSC code : 3403.2 & 1612.5 |
|---|---|
| Requires | Per Site Development check sheet provided by Ericka Koss: B) Floodwater openings shall be located on two different sides of the enclosed area. |
| Code Modification or Alternate Requested | |
| Proposed Design | The two required openings will be provided along the West side of the enclosed are only. Refer to attached floor plan and elevation. |
| Reason for alternative | Due to the NW corner location of the defined enclosed area (trash room & exit stair landing) a flood water opening cannot be provided on the North side of the building due the zero lot-line property line location. Refer to attached partial plan of the area. |
Appeal item 4
| Code Section | 703.3 |
|---|---|
| Requires | The application of any of the alternate methods listed in this section shall be based on the fire exposure and acceptance criteria specified in ASTM E119 or UL 263. The required fire resistance of a building element, component or assembly shall be permitted to be established by any of the following methods or procedures: 1.Calculations in accordance with Section 722. |
| Code Modification or Alternate Requested | |
| Proposed Design | The building being renovated is Towne Storage in the city of Portland, Oregon and is currently in compliance with Type IIIB construction. The building is now classified as Type IIIA. Under Type IIIA construction, the typical floor construction and associated secondary members must have a minimum one-hour fire resistance rating. The proposed design involves locating structural steel drag struts within an approved 1 hour floor assembly as follows: The assembly is required to be listed, approved, 1-hour fire-resistance-rated construction per OSSC 602. There is no known tested assembly that matches the provided assemblies. See the attached floor plan for extent of the drag strut, and the attached engineering judgment letter for assembly details. |
| Reason for alternative | The proposed design uses an analysis from an Oregon registered Fire Protection Engineer to provide equivalent life safety and fire protection to what the code requires. The drag strut is being inserted into an assembly approved by appeal 13471, therefore we request that this appeal be granted. |
Appeal Decision
1. Roof deck located above maximum number of stories: Granted per ICC approved 2018 IBC model code change lifting restriction on location of roof decks in a fully sprinkled building. Elements or structures enclosing the occupied roof areas shall not extend more than 48" inches above the surface of the occupied roof.
2. Reduction of minimum dimension of Fire Command Center from 10' to 8': Granted provided the final equipment layout is approved by the Fire Marshal's Office.
3. Location of flood openings on one side only: Granted as proposed.
4. Unprotected steel drag struts incorporated into alternative fire rated floor assembly: HOLD for structural analysis showing that the structure remains intact and is adequate to carry gravity loads if unprotected steel elements, including drag strut and steel angles are removed.
For the items granted, the Administrative Appeal Board finds that the information submitted by the appellant demonstrates that the approved modifications or alternate methods are consistent with the intent of the code; do not lessen health, safety, accessibility, life, fire safety or structural requirements; and that special conditions unique to this project make strict application of those code sections impractical.
Pursuant to City Code Chapter 24.10, you may appeal this decision to the Building Code Board of Appeal within 180 calendar days of the date this decision is published. For information on the appeals process and costs, including forms, appeal fee, payment methods and fee waivers, go to www.portlandoregon.gov/bds/appealsinfo, call (503) 823-7300 or come in to the Development Services Center.
See something we could improve on this page? Give website feedback.