Appeal 14850
Appeal Summary
Status:
Appeal ID: 14850
Submission Date: 3/25/17 9:59 AM
Hearing Date:
Case #:
Appeal Type: Building
Project Type: commercial
Building/Business Name: Multnomah County
Appeal Involves: Alteration of an existing structure,Addition to an existing structure
Proposed use: Courthouse
Project Address: 1200 SW 1st Ave.
Appellant Name: Tom Jaleski
LUR or Permit Application #: Preliminary
Stories: 17 Occupancy: A3, B, F1, S1 Construction Type: 1A
Fire Sprinklers: Yes - Throughout
Plans Examiner/Inspector: Jody Orrison
Plan Submitted Option: pdf [File 1] [File 2] [File 3] [File 4] [File 5] [File 6] [File 7] [File 8] [File 9]
Payment Option: electronic
Appeal Information Sheet
Appeal item 1
| Code Section | 722.2.4.2 Minimum cover for R/C columns. |
|---|---|
| Requires | The minimum thickness of concrete cover to the main longitudinal reinforcement in columns, regardless of the type of aggregate used in the concrete and the specified compressive strength of concrete, f 'c, shall not be less than 1 inch (25 mm) times the number of hours of required fire resistance or 2 inches (51 mm), whichever is less. |
| Code Modification or Alternate Requested | |
| Proposed Design | Six existing columns are located along j4 column line on the south sides of the hearing rooms. The 20x20 columns exceed a 4 hr rating per OSSC §722.2.4, but the minimum existing concrete cover over columns is only 1 inch. Additional fire resistance will be provided through equivalent surface fire protection coating per NTRL tested assemblies. |
| Reason for alternative | The R/C column is required to be 3-hour fire-resistance rated per OSSC Table 601. The Column is 20x20, exceeding the minimum dimension per 722.2.4, but the concrete cover provided does not meet the prescriptive requirements of 722.2.4.2 to achieve a 3-hour rating. In lieu of increasing concrete cover thickness, additional fire protection will be provided by intumescent coating. |
Appeal item 2
| Code Section | 721.5.1 Fire Resistance for Structural Steel Columns. |
|---|---|
| Requires | The Fire-resistance rating of steel columns shall be based on the size of the element and the type of protection provide in accordance with this section. |
| Code Modification or Alternate Requested | |
| Proposed Design | Six existing 20x20 concrete columns located along j4 column line on the south sides of the hearing rooms will be supplemented with adjacent new steel columns to form a new assembly. Passive fire Protection requirements of the steel were compared to code minimum requirements of OSSC Table 601. The steel will be protected with Intumescent coating per UL design testing to achieve 3 hr rating. |
| Reason for alternative | The new steel columns are comprised of significantly thicker steel than the compared UL tested assemblies which provide greater intrinsic fire resistance. Once the added fire protection coating is applied, the members will maintain a greater fire resistance rating than prescriptive requirement. |
Appeal item 3
| Code Section | 722.2.4.2 Minimum cover for R/C columns. |
|---|---|
| Requires | The minimum thickness of concrete cover to the main longitudinal reinforcement in columns, regardless of the type of aggregate used in the concrete and the specified compressive strength of concrete, f 'c, shall not be less than 1 inch (25 mm) times the number of hours of required fire resistance or 2 inches (51 mm), whichever is less. |
| Code Modification or Alternate Requested | |
| Proposed Design | Several existing (stand-alone) concrete columns are located along grids j4 and j8. See attached plan diagrams for relevant locations. The 20x20 columns exceed a 4 hr rating per OSSC §722.2.4, but the minimum existing concrete cover over columns is only 1 inch. These columns will be protected with SFRM to achieve a 3-hour minimum fire resistance rating. |
| Reason for alternative | The R/C column is required to be 3-hour fire-resistance rated per OSSC Table 601. The Column is 20x20, exceeding the minimum dimension per 722.2.4, but the concrete cover provided does not meet the prescriptive requirements of 722.2.4.2 to achieve a 3-hour rating. In lieu of increasing cover thickness, additional fire protection will be provided by SFRM. |
Appeal item 4
| Code Section | 721.5.1 Fire Resistance for Structural Steel Columns. |
|---|---|
| Requires | The Fire-resistance rating of steel columns shall be based on the size of the element and the type of protection provide in accordance with this section. |
| Code Modification or Alternate Requested | |
| Proposed Design | Several new steel columns will be added to the Jefferson Station structure. See attached plan diagrams. Passive fire Protection requirements of the steel were compared to code minimum requirements of OSSC Table 601. The steel will be protected with SFRM per UL design testing to achieve 3 hr rating. |
| Reason for alternative | The new steel columns are compared UL tested assemblies and provide equivalent fire resistance. Once the fire protection coating is applied, the members will maintain a greater fire resistance rating than the prescriptive requirement. |
The administrative staff has not yet reviewed this appeal.