Appeal 18389
Appeal Summary
Status: Decision Rendered
Appeal ID: 18389
Submission Date: 9/2/18 6:32 PM
Hearing Date: 9/5/18
Case #: B-023
Appeal Type: Building
Project Type: commercial
Building/Business Name: Eastside Office Building
Appeal Involves: Erection of a new structure
Proposed use: Office building with retail/restaurant uses at ground floor, single level below grade parking
Project Address: 525 SE MLK Jr Blvd
Appellant Name: Tom Jaleski
LUR or Permit Application #: Permit 16-289173-LU
Stories: 6 Occupancy: A-2, A-3, S-2, B Construction Type: III-A
Fire Sprinklers: Yes - Throughout
Plans Examiner/Inspector: John Cooley, Corey Stanley
Plan Submitted Option: pdf [File 1] [File 2]
Payment Option: mail
Appeal Information Sheet
Appeal item 1
| Code Section | OSSC §903.3.1.1, NFPA 13 8.17.1 |
|---|---|
| Requires | NFPA 13 as referenced by 2014 OSSC §903.3.1.1., Standard NFPA 13, |
| Code Modification or Alternate Requested | |
| Proposed Design | This project is a 6-story office building with Cross-laminated timber (CLT) panels as the floor framing. The exterior canopy assembly is located above the main entrance, approximately 11 feet above the sidewalk. The canopy extends for approximately 36’-4” along the east wall (see Figure 1) and 6’-5 5/8” wide. The area underneath the canopy is used exclusively as a sidewalk for pedestrians. No storage of combustibles will be located directly underneath the canopy. The exterior wall of the building is constructed of noncombustible materials in accordance with OSSC §602.3 and combustible exterior projections allowed per OSSC section 705.2.2. The proposed canopy assembly will be constructed of noncombustible steel frame, as well as a solid Cross Laminated Timber (CLT) underside finish (non-structural). The surface of the wood will be treated with Flamestop II stain (see attached), which is a penetrating wood preservative treatment to reduce flame spread of wood to that of a Class A material as defined in OSSC §803.1.1. Because the canopy projection exceeds 4 ft in width, the space below the canopy must either by sprinklered or meet the requirements of NFPA 13 §8.15.7.2, §8.15.7.3. These sections permit the omission of sprinklers in exterior canopies where the following exist: The CLT panels are too large to be factory fire-retardant treated, and thus an alternate solution is required to protect the canopy CLT panel. The CLT finish will be protected with a field applied, fire-retardant penetrating treatment. The finishing seal forms a slight intumescent foam layer and carbon char when the treated wood is exposed to fire, minimizing the potential for flame propagation or smoke evolution. (See Intertek E84 Test-Attached) Fire Coating Flame Stop II will not require reapplication if not exposed directly to weather. (Recommended inspection at 5-year intervals) It is not anticipated that a credible fire scenario will occur inside the canopy assembly as the only source of ignition are UL listed recessed lights. The canopy structure is limited to non-combustible materials and an air gap is provided to ensure heat cannot build up during an event. We examined credible fire scenarios below the canopy, and the effect they will have upon CLT surfacing. The canopy bottom is to be installed a minimum height of 11 ft. above the exterior grade/finished sidewalk elevation. Potential fire scenarios include; a fire that may occur within an exterior trash can left underneath the canopy, or packages on the sidewalk. The canopy is open to the exterior on three sides. Since the flames would not be able to directly impinge upon the assembly and the canopies are open on three sides, heat will not be able to collect underneath the canopy at a rate similar to those experienced within the ASTM E 119 test furnace. It is anticipated that the CLT ignition point (550 degrees) from a credible fire scenario underneath the canopies would be nearly impossible. With surface treatment penetrating into the wood surface on all exposed sides, the material would match the surface burning characteristics of generally accepted (non-combustible) tropical hardwoods. This Appeal is similar in intent as to past granted appeals in canopy/overhangs with wood. 13089, 6 ft overhang using surface treatments |
| Reason for alternative | In the attached EJ, prepared by an Oregon Registered Fire Protection Engineer, we have reviewed the proposed canopy assembly to NFPA 13 requirements for sprinkler protection. Appeals in the past have successfully been granted with the use of tropical hardwood materials which have a low potential surface flame spread. The CLT panel proposed with the penetrating surface treatment, will meet the surface fire resistance of those wood materials with a Class A fire rating. |
Appeal Decision
Omission of sprinklers under canopy: Granted provided there is no combustible storage or furnishings located beneath the canopy.
Appellant may contact John Butler (503 823-7339) with questions.
The Administrative Appeal Board finds with the conditions noted, that the information submitted by the appellant demonstrates that the approved modifications or alternate methods are consistent with the intent of the code; do not lessen health, safety, accessibility, life, fire safety or structural requirements; and that special conditions unique to this project make strict application of those code sections impractical.
Pursuant to City Code Chapter 24.10, you may appeal this decision to the Building Code Board of Appeal within 180 calendar days of the date this decision is published. For information on the appeals process and costs, including forms, appeal fee, payment methods and fee waivers, go to www.portlandoregon.gov/bds/appealsinfo, call (503) 823-7300 or come in to the Development Services Center