Appeal 20454
Appeal Summary
Status: Mixed Decision. Items 1, 2, 4, 5 and 6: Decision Rendered. Item 3: Hold for Additional Information
Appeal ID: 20454
Submission Date: 5/24/19 4:19 PM
Hearing Date: 5/29/19
Case #: B-009
Appeal Type: Building
Project Type: commercial
Building/Business Name: 1500 Taylor Apartments
Appeal Involves: Erection of a new structure
Proposed use: Mixed-Use/Residential
Project Address: 1500 SW Taylor St
Appellant Name: Charles Kidwell
LUR or Permit Application #: LUR 18-281556-LU
Stories: 7 Occupancy: S-2, M, B, R-2 Construction Type: I-A, III-A
Fire Sprinklers: Yes - Throughout
Plans Examiner/Inspector: Steven Mortensen, Corey Stanley
Plan Submitted Option: pdf [File 1] [File 2] [File 3] [File 4] [File 5] [File 6] [File 7] [File 8] [File 9] [File 10] [File 11] [File 12] [File 13] [File 14] [File 15] [File 16]
Payment Option: mail
Appeal Information Sheet
Appeal item 1
Code Section | Sections 510.2 & 510.9 |
---|---|
Requires | 510.2 Horizontal building separation allowance. A building shall be considered as separate and distinct
occupancy uses, each with an occupant load of less 300, or Group B, M, R or S occupancies.
sprinkler system in accordance with Section 903.3.1.1, and shall be permitted to be any of the following
building having the smaller allowable height as measure from the grade plane. |
Code Modification or Alternate Requested | |
Proposed Design | The proposed project consists of a 5 Story Type IIIB Construction Residential building above a 2 Level |
Reason for alternative | Section 510 Special Provisions allows for use of Horizontal Assemblies to created separate buildings that are |
Appeal item 2
Code Section | 602.3 Type III Construction |
---|---|
Requires | Type III construction is that type of construction in which the exterior walls are of noncombustible materials and the |
Code Modification or Alternate Requested | |
Proposed Design | The Proposed Design consists of a 5 Story Type IIIA Construction Residential building above a 2 Level |
Reason for alternative | FRT reduces the structural strength of wood and requires more wood than a non-FRT wood wall. |
Appeal item 3
Code Section | Multiple OSSC Sections |
---|---|
Requires | High-rise buildings shall comply with Sections 403.2 through 403.6 |
Code Modification or Alternate Requested | |
Proposed Design | The Proposed Design consists of a 5 Story Type IIIA Construction Residential building above a 2 Level |
Reason for alternative | The Proposed Design consists of a 5 Story Type IIIA Construction Residential building above a 2 Level Type |
Appeal item 4
Code Section | OSSC 1018.6 and BDS Code Guide OSSC/10/#9 |
---|---|
Requires | Corridor Continuity and Equipment & Furniture Allowances
an automatic sprinkler system meeting the requirements of NFPA 13.
a. The egress path must be shown on the submitted plans; |
Code Modification or Alternate Requested | |
Proposed Design | PROPOSED DESIGN SUMMARY: |
Reason for alternative | The Proposed Corridor and Lobby Design has a 1-Hour rated Corridor system serving the First Floor Level. |
Appeal item 5
Code Section | NFPA 110, Sections 7.2.1.1 and 7.7.2.3 |
---|---|
Requires | The emergency generator room must be separated from the rest of the building by construction |
Code Modification or Alternate Requested | |
Proposed Design | The generator radiator exhaust is ducted through the garage and up to terminate at an area well and |
Reason for alternative | The limited amount of exterior wall does not allow for both the intake and the exhaust air to be |
Appeal item 6
Code Section | OSSC 2902 Minimum Plumbing Facilities |
---|---|
Requires | 2902.1 Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy or use of |
Code Modification or Alternate Requested | |
Proposed Design | a. The design includes a single occupant Toilet Room on the ground level adjacent to the |
Reason for alternative | residents of the apartment buildings and their guests as well as prospective renters meeting |
Appeal Decision
1. Increase from 1 story to 2 stories of Type IA construction below the 3 hour horizontal separation: Granted provided all provisions of 2015 IBC section 510.2 are met and overall building height is limited to that allowed for proposed IIIA construction.
Note: The Board determines the 3 hour separation is required only between the Type 1A building and the Type IIIA building and creates a total of 2 buldings, not three.
2. Use of non-fire resistant treated wood in exterior walls of Type III construction: Granted provided
a). mineral wool insulation is installed in all exterior walls and;
b). provided the Code Guide Condition 17 graphic detail drawings are used with the exception of requirements for sacrificial studs and;
c). provided a Special Inspection is performed on the installation of the mineral wool.
3. Exterior deck located above 75 feet with partial use of highrise requirements: Hold for additional information.
4a. Corridor continuity through lobby: Granted as proposed.
4b. Type 13 water curtain sprinkler protection at non-fire rated glazed openings in one hour fire rated lobby wall: Granted provided windows are non-operable, doors are on closers and sprinklers are spaced not more than 6 feet apart and placed a minimum of 6 inches and a maximum of 12 inches from the opening(s) and a maximum of 12 inches below the ceiling. Sprinklers are to be installed on both sides of the openings. A separate permit from the Fire Marshal’s Office is required.
5a. Standby generator with intake air from parking garage: Denied. Proposal does not provide equivalent Life Safety protection.
5b. Generator louevers in two hour enclosure with sprinkler head on each side in lieu of fire damper: Denied. Proposal does not provide equivalent Life Safety protection.
6. Reduction in minimum required plumbing fixtures in tenant only amenity spaces: Granted provided 1st floor toilet room is available for general use and provided signage is located at amenity spaces with location of toilet room.
For item 3 appellant may contact Corey Stanley (971 291-8919) with questions.
For other items appellant may contact John Butler (503 823-7339) with questions.
For items 1, 2, 4 and 6. The Administrative Appeal Board finds that the information submitted by the appellant demonstrates that the approved modifications or alternate methods are consistent with the intent of the code; do not lessen health, safety, accessibility, life, fire safety or structural requirements; and that special conditions unique to this project make strict application of those code sections impractical.
Pursuant to City Code Chapter 24.10, you may appeal this decision to the Building Code Board of Appeal within 180 calendar days of the date this decision is published. For information on the appeals process and costs, including forms, appeal fee, payment methods and fee waivers, go to www.portlandoregon.gov/bds/appealsinfo, call (503) 823-7300 or come in to the Development Services Center.
For item 5. Pursuant to City Code Chapter 24.10, you may appeal this decision to the Building Code Board of Appeal within 180 calendar days of the date this decision is published. For information on the appeals process and costs, including forms, appeal fee, payment methods and fee waivers, go to www.portlandoregon.gov/bds/appealsinfo, call (503) 823-7300 or come in to the Development Services Center.