Appeal 23953

Appeal Summary

Status: Decision Rendered - Held over from ID 23909 (7/29/20) for additional information

Appeal ID: 23953

Submission Date: 8/12/20 11:00 AM

Hearing Date: 8/19/20

Case #: B-002

Appeal Type: Building

Project Type: commercial

Building/Business Name: adidas North Building

Appeal Involves: Erection of a new structure

Proposed use: Business

Project Address: 5060 N Greeley Ave

Appellant Name: Eric Mishler

LUR or Permit Application #: Permit 18-188494-CO

Stories: 11 Occupancy: Type IA, III-A Construction Type: Commercial

Fire Sprinklers: Yes - B4 - 6

Plans Examiner/Inspector: Brian McCall, Corey Stanley

Plan Submitted Option: pdf   [File 1]

Payment Option: electronic

Appeal Information Sheet

Appeal item 1

Code Section

703.2

Requires

Where materials, systems or devices that have not been tested as part of a fire-resistance rated assembly are incorporated into the building element component, or assembly, sufficient data shall be made available to the building official to show that the required fire-resistance rating is not reduced.

Provide a tested and rated assembly angles, plates, and HSS steel in a horizontal assembly or provide an approved building code appeal for the proposed installations.

Code Modification or Alternate Requested

Method of maintaining the fire resistance rating of steel angle in accordance with ANSI/UL 263, ASTM E119

Proposed Design

Propose protecting the 3/8" tip of the steel angle with CAFCO SprayFilm WB5. The thickness of the SprayFilm will be 105 mils and will taper a minimum of 2" onto the surface of the CAFCO-BOARD and the surrounding concrete.

Reason for alternative

Project conditions exist where a structural steel angle supporting precast concrete slabs. The angles have been protected with CAFCO-BOARD; however, the 3/8" tip of the angle have been left exposed due to obstructions (conduit). Reference Appeal ID #22173 and #23909.

Reference Appeal Letter attached on page 4

Appeal Decision

Alternate 3 hour fire rating of structural steel angles: Granted as proposed.

The Administrative Appeal Board finds that the information submitted by the appellant demonstrates that the approved modifications or alternate methods are consistent with the intent of the code; do not lessen health, safety, accessibility, life, fire safety or structural requirements; and that special conditions unique to this project make strict application of those code sections impractical.

Pursuant to City Code Chapter 24.10, you may appeal this decision to the Building Code Board of Appeal within 90 calendar days of the date this decision is published. For information on the appeals process, go to www.portlandoregon.gov/bds/appealsinfo, call (503) 823-7300 or come in to the Development Services Center.