Appeal 27917
Appeal Summary
Status: APPROVED
Appeal ID: 27917
Submission Date: 7/25/22 10:17 AM
Hearing Date: 7/28/22
Case #: 22-41
Appeal Type: Fire
Project Type: commercial
Building/Business Name: Alder House Apartments
Appeal Involves: Alteration of an existing structure
Proposed use: Multi-family
Project Address: 523 SW 13th
Appellant Name: Brandon Koonz
LUR or Permit Application #: Permit 22-150814 FS
Stories: 7 Occupancy: S-2, B, R-2 Construction Type: I-B
Fire Sprinklers: Yes - Throughout
Plans Examiner/Inspector: Jerome Perryman
Plan Submitted Option: pdf [File 1]
Payment Option: electronic
Appeal Information Sheet
Appeal item 1
| Code Section | PFC 5704.2.7.5.6 |
|---|---|
| Requires | Filling connections for Class I, II & IIIA liquids that are made or broken shall be located outside the building, and not less than 5 feet away from building openings. |
| Code Modification or Alternate Requested | Propose to locate the remote fill station inside the parking entryway. |
| Proposed Design | The fuel fill station will be located within the building footprint on the west wall of the parking entry. This space is open to the sidewalk and street at all times, and separated from parking area by a security gate/grill and man-door located more than 5' from the proposed location. The location will also be within line of site of a fuel truck parked in front of the building. |
| Reason for alternative | This an existing building. The ground floor walls adjacent to areas where a fuel truck could park are made up of doors and windows. Areas without doors and windows are not near fuel truck parking. |
Appeal Decision
The Administrative staff has reviewed your appeal regarding the remote fill site for a diesel driven fire pump and the appeal is granted as proposed.