Appeal 31931

Appeal Summary

Status: Decision Rendered

Appeal ID: 31931

Submission Date: 10/11/23 5:39 PM

Hearing Date: 10/18/23

Case #: B-012

Appeal Type: Building

Project Type: commercial

Building/Business Name: Troy Laundry

Appeal Involves: other: Phase opening of on going construction project

Proposed use: Social Club

Project Address: 1025 SE Pine St

Appellant Name: Mike Zupan

LUR or Permit Application #: Permit 20-215321-CO

Stories: 3 Occupancy: Construction Type: Seismic Retrofit

Fire Sprinklers: Yes - Everywhere

Plans Examiner/Inspector: Fred Barsukoff, Guy Altman, Jeff Herman

Plan Submitted Option: pdf   [File 1]

Payment Option: mail

Appeal Information Sheet

Appeal item 1

Code Section

111.3

Requires

Open permit (20-215321-CO) is for the entirety of the building (basement, level 1, level 2, and level 3). The building official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely.

Code Modification or Alternate Requested

We are requesting a revision to the permit to accommodate a phased turnover of the building, seeking a TCO for the basement, level 1, and level 2 while level 3 completes construction.

Proposed Design

As shown in the supplemental documents, a separate construction entrance will be utilized to access the ongoing construction on the level 3. Guests occupying levels 1 and 2 will utilize the main entrance on SE Pine Street, main stair (ST-3), and guest elevator. The construction team will utilize the loading dock entrance on SE 10th Ave, the back-of-house stairs (ST1-1), and the back-of-house elevator.

The fire alarm and fire sprinkler will be fully functioning on the occupied floors (basement, level 1, and level 2), and health department and elevator inspections will be complete. A temporary partition will be utilized at the stair wells between level 2 and level 3 as a safety measure to ensure guests do not access the active construction area. The guest elevator will be locked out to level 3, ensuring guest access is restricted to levels 1 and 2. Construction materials for level 3 will be delivered off hours and hoisted via crane positioned on SE 10th Ave to avoid conflicts with guests utilizing the main entrance.

Reason for alternative

Level 3 is primarily exterior space which is not desirable for guests during the winter months. This change allows guests to access level 1 and level 2 early while level 3 is completed. The phased TCO logistics plans ensures equivalent health, accessibility, life safety and fire protection until the entire building is complete.

Appeal Decision

Phased turnover of building with a seeking a TCO for the basement, level 1, and level 2 while level 3 construction in progress: Denied. Proposal does not provide an equivalent level of Life Safety protection.

Appellant may contact Guy Altman (503-865-6527) with questions.

PLEASE READ THE NOTE BELOW when providing Board requested Additional Information or when submitting a reconsideration after 1st time appeal Denial.

A reconsideration is submitted online following the same submittal process and using the same appeals form as the original appeal. Indicate at the beginning of the appeal form that you are filing a reconsideration and include the original assigned Appeal ID number. The reconsideration will receive a new appeal number.

Include the original attachments and appeal language. Provide new text with only that information that is specific to the reconsideration in a separate paragraph(s) clearly identified as "Reconsideration Text" with any new attachments also referenced. Once submitted, the appeal cannot be revised.

No additional fee is required when the Board has requested additional information or for the first reconsideration of a denied appeal if submitted within 6 months of the original appeal. In these two specific instances please ignore the auto-generated request for another fee.

PLEASE NOTE that there will be no auto-generated verification that the appeal is successfully submitted. To verify this by viewing the submitted appeal, go to;

https://www.portlandoregon.gov/bds/appeals/?action=search .

Then click on "SEARCH" and you will see the most recent 500 appeals in order that they have been filed. Find your appeal, click on "view" and then on "file". You can also refine the results by filling in a search word such as your name.

Pursuant to City Code Chapter 24.10, you may appeal this decision to the Building Code Board of Appeal within 90 calendar days of the date this decision is published.  For information on the appeals process, go to www.portlandoregon.gov/bds/appealsinfo, call (503) 823-6251 or come to the Development Services Center.