Appeal 32364
Appeal Summary
Status: Decision Rendered
Appeal ID: 32364
Submission Date: 6/20/24 4:39 PM
Hearing Date: 7/3/24
Case #: B-001
Appeal Type: Building
Project Type: commercial
Building/Business Name: Tiller Terrace
Appeal Involves: Erection of a new structure
Proposed use: Apartment / Mixed-use
Project Address: 1670 SW ALDER ST
Appellant Name: Charlie Baxter
LUR or Permit Application #: Permit 20-135027- CO
Stories: 6 Occupancy: A, B, R-2, S-1, S-2 Construction Type: I-A / III-A
Fire Sprinklers: Yes - All
Plans Examiner/Inspector: Sean Vanderjagt
Plan Submitted Option: pdf [File 1] [File 2] [File 3] [File 4]
Payment Option: electronic
Appeal Information Sheet
Appeal item 1
| Code Section | NFPA 110, 2014 OSSC Sections 7.2.1.1 and 7.7.2.3, and OMSC 607.5.2 |
|---|---|
| Requires | Ducts and air transfer openings that penetrate fire barriers shall be protected with listed fire dampers installed in |
| Code Modification or Alternate Requested | The intent of the appeal is to allow deluge sprinkler heads at opening in lieu of the fire/smoke damper. |
| Proposed Design | This appeal would allow an emergency generator intake vent in a 2 hour rated wall without a fire damper and added deluge sprinkler heads. The on-site generator is now located in the basement Level P1. The generator room requires a two-hour rated enclosure (fire barrier) constructed in accordance to OSSC Section 707. The generator requires ventilation air for cooling purposes. If the openings in the two-hour wall were protected with fire smoke dampers, this would disable the generator because it would prevent combustion and cooling air from reaching the generator in cases of emergency. The engine radiator cooling airflow is 10,800 cubic feet per minute. The relief air is ducted directly from the exterior via a louver in the generator room. The generator flue exhaust of 1,200 cfm is being taken to the exterior wall on level 1 in a 2-hour shaft. The total generator intake of 12,000 cubic feet per minute is drawing air from the garage via a 24 square foot opening. The proposed design that will be implemented to provide an equivalent level of protection to the generator enclosure will include: |
| Reason for alternative | Due to Planning Department’s requirement for the layout of the building, the generator is located within the limits of the building enclosure. This location makes it not possible to provide both intake and exhaust louvers on the non-rated exterior wall. The intake louver has been located in the east wall of the two-hour rated enclosure. The current layout positions the generator enclosure within the type IA portion of the building, and the enclosure can only be accessed by property management. Reference appeal with similar condition: Appeal ID#13885, 13519, 6/1/16; Appeal ID#12880, 12/30/15; Appeal ID#12693, 11/12/15; Appeal ID#16416, 11/31/18 |
Appeal Decision
Sprinkler protection in lieu of fire dampers at intake opening for emergency generator located in two hour enclosure: Granted provided sprinklers are placed a minimum of 6 inches and a maximum of 12 inches from the opening and a maximum of 12 inches below the ceiling. Sprinklers are to be installed on both sides of the opening. A separate permit from the Fire Marshal’s Office is required.
"The Administrative Appeal Board finds that the information submitted by the appellant demonstrates that the approved modifications or alternate methods are consistent with the intent of the code; do not lessen health, safety, accessibility, life, fire safety or structural requirements; and that special conditions unique to this project make strict application of those code sections impractical.
Pursuant to City Code Chapter 24.10, you may appeal this decision to the Building Code Board of Appeal within 90 calendar days of the date this decision is published. For information on the appeals process, go to www.portlandoregon.gov/bds/appealsinfo, call (503) 823-6251 or come to the Development Services Center."