Appeal 32376

Appeal Summary

Status: Decision Rendered

Appeal ID: 32376

Submission Date: 6/26/24 5:07 PM

Hearing Date: 7/3/24

Case #: B-006

Appeal Type: Building

Project Type: commercial

Building/Business Name:

Appeal Involves: occ Change from R3 to R3 - residential transient living units,other: Transient, less than 10 occupants

Proposed use: Residence - Transient Living (R3)

Project Address: 508-520 NE 56th Ave

Appellant Name: Will Uebelacker

LUR or Permit Application #: Permit 22-138465-CO

Stories: 4 Occupancy: R-3 Construction Type: V-B

Fire Sprinklers: Yes - NFPA 13D throughout

Plans Examiner/Inspector: Steven Freeh

Plan Submitted Option: pdf   [File 1]   [File 2]   [File 3]

Payment Option: electronic

Appeal Information Sheet

Appeal item 1

Code Section

Table 504.4

Requires

Requires four stories in an R-3 occupancy to be equipped with a fire suppression system of 13R or 13 system, 13D is only allowed up to three stories.

Code Modification or Alternate Requested

We are proposing to keep NFPA 13D sprinklers rather than 13R or 13.

Proposed Design

NFPA 13D sprinklers are installed throughout the building including the fourth floor attic space that is unfinished and not intended for occupancy.

Reason for alternative

Per 903.3.1.3 NFPA 13D sprinkler systems are allowed in group R-3 and specifically townhouses. When built, the attic was never classified as an additional story, however, now as a commercial building the unfinished attic is being counted even if it will not be occupied. The building was built per the residential code for townhouse construction and will be used in a near identical manner. NFPA 13D sprinklers have been installed throughout the building including the attic space. Installing a 13R system would be cost prohibitive when the 13D system provides comparative fire coverage.

Appeal item 2

Code Section

706.4

Requires

Fire walls shall have a fire-resistance rating of not less than 2 hours for group R-3.

Code Modification or Alternate Requested

We are proposing to keep the residential townhouse demising wall as originally constructed to meet R302.2.1(1) with two 1-hour fire-resistant rated wall assemblies.

Proposed Design

Built under the residential code, this required townhouse separation by 2-hour fire resistant rated wall assemblies. The project met this requirement with the use of two 1-hour fire rated firewalls, one on each side of the common property line. Each 1-hour rated firewall has a layer of 5/8” type ‘X’ gypsum board on the interior side, 15/32” APA rated structural sheathing, 2x6 stud framing filled with insulation, and a 1” air gap centered on the property line. The fireblocking has been installed at the floor and ceiling joists, and fire rated roof sheathing extends 4 feet on either side of the 2-hour fire resistant fire wall. For additional protection, an NFPA 13D sprinkler has been installed throughout the building that was not required under the residential code.

Reason for alternative

The commercial building code requires a 2-hour fire resistant firewall and does not make the same distinction as the residential code for the allowance of two 1-hour fire resistant rated walls. The addition of an NFPA 13D sprinkler adds an extra layer of safety to the townhouse construction not originally required. The building is changing from an R3 townhouse to R3 transient use and will be occupied and used in the same manner. Adding an additional layer of 5/8” gyp to both sides of the residential code classified 2 hour fire wall (two 1-hour fire rated walls) would costly to install on four levels from foundation to underside of roof sheathing.

Appeal item 3

Code Section

706.5

Requires

Fire walls shall be continuous from exterior wall to exterior wall and shall extend not less than 18 inches beyond the exterior surface of exterior walls.

Code Modification or Alternate Requested

That the use of an NFPA 13D sprinkler system be an acceptable alternative means for complying with 903.3.1.2 (see Appeal 1), and noncombustible sheathing used in the roof construction as part of the two 1-hour fire rated wall system be utilized to meet exception 3 of 706.5.

Proposed Design

The existing two 1-hour rated firewalls that separate the unit townhouses extends to the underside of the roof sheathing, including the layer of 5/8” type ‘X’ gypsum board on each side. Fire retardant plywood sheathing is used for a distance of 4 feet extending out on either side of the imaginary property line. Each townhouse has been equipped throughout with NFPA 13D sprinklers for additional protection.

Reason for alternative

The firewalls as built terminate at the underside of the noncombustible exterior sheathing and the building is now equipped with an automatic sprinkler system. The use of NFPA 13D should be allowed to remain in lieu of a 13 or 13R system that provides similar coverage. In addition, no roof openings are within 4 feet of the two 1-hour rated firewall that extends to the underside of the noncombustible roof sheathing.

Appeal Decision

"1) NFPA 13D sprinkler system instead of NFPA 13R sprinkler system for determining number of allowed stories: Denied. The proposal does not provide equivalent fire and life safety.
2) Two 1-hour fire-resistance-rated walls instead of one 2-hour-rated fire wall: Denied. The proposal does not provide equivalent fire and life safety.
3) NFPA 13D sprinkler system instead of NFPA 13R system for purposes as meeting 706.5 exception 3: Denied. The proposal does not provide equivalent fire and life safety."The appellant may contact Steve Freeh (503-865-6535) with questions.

"PLEASE READ THE NOTE BELOW when providing Board requested Additional Information or when submitting a reconsideration after 1st time appeal Denial.

A reconsideration is submitted online following the same submittal process and using the same appeals form as the original appeal. Indicate at the beginning of the appeal form that you are filing a reconsideration and include the original assigned Appeal ID number. The reconsideration will receive a new appeal number.

Include the original attachments and appeal language. Provide new text with only that information that is specific to the reconsideration in a separate paragraph(s) clearly identified as ""Reconsideration Text"" with any new attachments also referenced. Once submitted, the appeal cannot be revised.

No additional fee is required when the Board has requested additional information or for the first reconsideration of a denied appeal if submitted within 6 months of the original appeal. In these two specific instances please ignore the auto-generated request for another fee.

PLEASE NOTE that there will be no auto-generated verification that the appeal is successfully submitted. To verify this by viewing the submitted appeal, go to;

https://www.portlandoregon.gov/bds/appeals/?action=search .

Then click on ""SEARCH"" and you will see the most recent 500 appeals in order that they have been filed. Find your appeal, click on ""view"" and then on ""file"". You can also refine the results by filling in a search word such as your name. Pursuant to City Code Chapter 24.10, you may appeal this decision to the Building Code Board of Appeal within 90 calendar days of the date this decision is published.  For information on the appeals process, go to www.portlandoregon.gov/bds/appealsinfo, call (503) 823-6251 or come to the Development Services Center."