Appeal 32382
Appeal Summary
Status: Decision Rendered
Appeal ID: 32382
Submission Date: 6/28/24 11:17 AM
Hearing Date: 7/10/24
Case #: B-004
Appeal Type: Building
Project Type: commercial
Building/Business Name: Kiley40
Appeal Involves: Erection of a new structure
Proposed use: R2 Dwelling units
Project Address: 3950 N Williams
Appellant Name: Bob Schatz
LUR or Permit Application #: Permit 24-029720-CO
Stories: 5 Occupancy: R2 and M Construction Type: 3B
Fire Sprinklers: Yes - Whole building
Plans Examiner/Inspector: Steve Freeh
Plan Submitted Option: pdf [File 1] [File 2] [File 3] [File 4]
Payment Option: electronic
Appeal Information Sheet
Appeal item 1
| Code Section | Table 705.8 |
|---|---|
| Requires | For a wall that is 10 to less than 15 feet from a property line, in a fire sprinklered building the allowable area of unprotected openings is 45% |
| Code Modification or Alternate Requested | To verify the term “Exterior Wall” in the description of this table to refer to the wall that separates the inside from the outside vs referring to the open space that is below a wall on the floor above the open space. |
| Proposed Design | The proposal is to consider the wall facing the property line on the first floor, which is the wall with a door in it accessing the outdoor space, as the wall with the unprotected openings and not consider the open space at the edge of the wall above it as a wall. |
| Reason for alternative | The area we are discussing is an open outdoor area on the first floor which is to be used by the tenants of the apartment building as common outdoor area. This area has walls on three sides and no wall on the 4th side, which is also open to an uncovered outdoor area, the area is also covered by a portion of the 2nd floor. The reason for the alternate is because the title of this section is describing the “area of exterior wall openings”. I am proposing that the exterior wall is the wall that is separating the inside from the outside, even if the outside is a covered outdoor space. I am being told by my plans examiner that the exterior wall is the open area/plane which is at the edge of the façade on the 2nd floor, which actually isn’t a wall at all but an open space. One reason I would propose the wall with the door in it is to be considered the exterior wall is this, if that wall is not the exterior wall then what is it called? An interior wall? That wall is currently a 2-hour fire rated wall to comply with the regulations of type 3B construction requiring exterior walls to have that fire rating. If that wall is considered an interior wall then am I to not fire rate that wall? If that wall with the door in it is interior then do I not insulate it as an exterior wall? A reason the open space should not be considered an exterior wall is it is really hard to insulate that wall to meet energy codes. Another reason to consider the wall with the door in it as an exterior wall is to follow the reason for this code in the first place. It seems the whole point of table 705.8 is to protect a structure from fire spreading from one building to the next by putting a fire rated wall in it’s path, with an acceptable amount of openings. If that covered open area on the first floor has at least 1-hour walls and ceiling I don’t see how that doesn’t meet this code, a fire approaching this space will be faced with fire rated assemblies. The only unprotected opening on the first floor in this area is the door in the wall to the outdoor space which is 25 feet from the property line. That is the only unprotected opening and that would be how a fire gets into a building, not through the fire rated walls or ceiling. And in this situation that door is meeting the unprotected opening code with plenty of room to spare. Another reason to consider is I am being told that the open space is considered an exterior wall because of the second floor above it ends at that spot. When I calculate the unprotected openings in a wall I have been told over the years that we count the wall to opening ratio elevation view per floor and not per elevation of the whole building. For example on just the second floor I take the wall area of that second floor and divide out just the windows on that second floor to get my percentage of unprotected openings on the second floor. I propose if that is the way we calculate the walls then the second floor wall has nothing to do with the first floor wall in this table, they are calculated separately. And if they are calculated separately it makes no sense to consider the open space under another story as a wall but would be better to consider the actual wall facing the property line as a wall. If you do want to consider the whole elevation as one exterior wall, and not calculate it floor at a time, then my whole wall is 1,714 square feet and I have 462 square feet of unprotected openings (including windows and this open area we are discussing) and the total unprotected openings add up to 27% and I am allowed 45%, see attached elevation. So I propose it meets this code either way you add it up but you need to pick one or the other. Here is another reason, the definition of exterior wall under chapter 2 is “A wall, bearing or nonbearing, that is used as an enclosing wall for a building, other than a fire wall, and that has a slope of 60 degrees or greater with the horizontal plane”. That seems to explain the wall with the door in it vs the open space I am being told I need to count as a wall. I propose that we consider the wall with the door in it as the exterior wall due to the definition of exterior wall. |
Appeal item 2
| Code Section | OFC 3303.1.1 |
|---|---|
| Requires | On site security during non-working construction times |
| Code Modification or Alternate Requested | Video Surveillance in replacement of on site security personnel. |
| Proposed Design | The proposed change is to have monitored Video Surveillance of the property. |
| Reason for alternative | Hiring on-site security is very expensive. We feel we can get the same protection, if not better, with Video Surveillance of the property. Our surveillance will be monitored by a professional surveillance company that will have access to on-site security when unwanted activity is noticed. Also this will aid in not only fire protection but in theft protection in the evenings and during the day. |
Appeal item 3
| Code Section | Table 716.1 |
|---|---|
| Requires | A 2-hour fire rated enclosure at interior exit stairways |
| Code Modification or Alternate Requested | Using a 2-hour shaft assembly under a staircase |
| Proposed Design | I will be using a 2-hour shaft assembly GA file #WP 7125 as the 2-hour assembly under a wood framed staircase to separate one stairway from another. You can see my stair section and details on attached sheet 8.1 and the assembly at detail K/2.0 |
| Reason for alternative | First reason is there is no fire rated assembly for staircases. Because of this the Portland appeals board has approved appeals of using shaft enclosure assemblies under staircases to meet required fire separations. I chose this assembly because it was a one-sided assembly as it’s easier to apply the entire assembly to just the underside of the staircase and not to both sides. This assembly was tested when applied to a 1 5/8” steel stud and it appears that the layers of gypsum and steel straps has little to do with the stud it’s attached to and appears that a wood stud, or stringer in this case, would perform the same way. This assembly also uses screws and not nails to hold it together and I feel would work best in this location. |
Appeal item 4
| Code Section | Section 1028.2 Exception 1.1 |
|---|---|
| Requires | Exits shall discharge directly to the exterior of the building: Not more than 50% of the required capacity of interior exit stairways is permitted to egress through areas on the level of discharge provided that all of the following conditions are met. Exception 1.1 Discharge of interior exit stairways shall be provided with a free and unobstructed path of travel to an exterior exit door and such exit is readily visible and identifiable from the point of termination of the enclosure. |
| Code Modification or Alternate Requested | That the exit is identifiable by signage. |
| Proposed Design | The proposal is to add an illuminated exit sign to be visible from the exit discharge, the door from the stairwell to the lobby. See location noted in red on the first floor plan. |
| Reason for alternative | Portland has been struggling with excessive crime which has led to at least this property owner to want the residents of this apartment building to feel safer within the entrance lobby by having less direct view from the front door at the sidewalk to the interior of the common space. This has resulted to the common hallway on the first floor to have a jog in it to obstruct views from the outside to the inside. This result has the opposite problem faced with this code of occupants not having direct view from the exit discharge to the exterior exit door. The design is not completely missing this section of the code, the requirement includes having a “free and unobstructed path of travel to an exterior exit door” which is does. The hallway is unobstructed and is 8’-10” wide right at the exit discharge and then is 6’-6” wide the rest of the way to the exterior exit door. 7 feet out of the exit discharge the exterior exit door is visible, the total distance from the exit discharge to the exterior exit door is 35 feet. It’s just the “readily visible from the point of termination of the enclosure” part of this exception that this design is not meeting. Due to that I am proposing adding an illuminated exit sign that is clearly visible from the exit discharge that points toward the exterior exit door, that would allow occupants to clearly identify which direction the exterior exit door is. |
Appeal Decision
1) Determination of "exterior wall": Denied. Proposal does not provide equivalent fire and life safety.
3) Alternate method for determining fire resistance rating of 2-hour shaft wall assembly: Hold for more information.
4) Allow exit signage to qualify as making an exterior exit door readily visible from the point of termination of an exit enclosure: Denied. Proposal does not provide equivalent life safety. Appellant may contact Steve Freeh (503-865-6535) with questions.
Item 2, please submit a fire code appeal to the Fire Appeals department for hearing.
"PLEASE READ THE NOTE BELOW when providing Board requested Additional Information or when submitting a reconsideration after 1st time appeal Denial.
A reconsideration is submitted online following the same submittal process and using the same appeals form as the original appeal. Indicate at the beginning of the appeal form that you are filing a reconsideration and include the original assigned Appeal ID number. The reconsideration will receive a new appeal number.
Include the original attachments and appeal language. Provide new text with only that information that is specific to the reconsideration in a separate paragraph(s) clearly identified as ""Reconsideration Text"" with any new attachments also referenced. Once submitted, the appeal cannot be revised.
No additional fee is required when the Board has requested additional information or for the first reconsideration of a denied appeal if submitted within 6 months of the original appeal. In these two specific instances please ignore the auto-generated request for another fee.
PLEASE NOTE that there will be no auto-generated verification that the appeal is successfully submitted. To verify this by viewing the submitted appeal, go to;
https://www.portlandoregon.gov/bds/appeals/?action=search .
Then click on ""SEARCH"" and you will see the most recent 500 appeals in order that they have been filed. Find your appeal, click on ""view"" and then on ""file"". You can also refine the results by filling in a search word such as your name. Pursuant to City Code Chapter 24.10, you may appeal this decision to the Building Code Board of Appeal within 90 calendar days of the date this decision is published. For information on the appeals process, go to www.portlandoregon.gov/bds/appealsinfo, call (503) 823-6251 or come to the Development Services Center."