Appeal 33402
Appeal Summary
Status: DECISION RENDERED
Appeal ID: 33402
Submission Date: 7/24/24 1:18 PM
Hearing Date: 7/31/24
Case #: B-008
Appeal Type: Electrical
Project Type: Residential
Building/Business Name: Riverplace Condominiums
Appeal Involves: Alteration of an existing structure
Proposed use: Residential
Project Address: 1730 S Harbor Way
Appellant Name: Hannah Theisen
LUR or Permit Application #: Other No permit
Stories: 5 Occupancy: Residential Construction Type: VB
Fire Sprinklers: Yes - in residences and common corridors
Plans Examiner/Inspector: Michael Silva
Plan Submitted Option: pdf [File 1] [File 2] [File 3] [File 4] [File 5]
Payment Option: electronic
Appeal Information Sheet
Appeal item 1
| Code Section | 18.4.6.1 18.4.6.2 18.4.6.3 |
|---|---|
| Requires | Audible low frequency devices required in sleeping areas. |
| Code Modification or Alternate Requested | Audible non-low frequency devices installed in units above door way to provide notification of a building fire alarm during FACP upgrade for elevator recall functions. |
| Proposed Design | System Sensor notification appliance has been installed to provide notification not provided by previous FACP. |
| Reason for alternative | This fire alarm system is being replaced due to elevator recall requirements. To minimize the need for dry wall repair in walls and ceilings but still provide better notification to residents of a building fire alarm. Sound pressure measurements have been provided to show effectiveness. |
Appeal Decision
Install non-low frequency devices in units above doorway for voluntary alarm system upgrade: Granted as proposed.
"The Administrative Appeal Board finds that the information submitted by the appellant demonstrates that the approved modifications or alternate methods are consistent with the intent of the code; do not lessen health, safety, accessibility, life, fire safety or structural requirements; and that special conditions unique to this project make strict application of those code sections impractical.
Pursuant to City Code Chapter 24.10, you may appeal this decision to the Building Code Board of Appeal within 90 calendar days of the date this decision is published. For information on the appeals process, go to www.portlandoregon.gov/bds/appealsinfo, call (503) 823-6251 or come to the Development Services Center."