Appeal 33422

Appeal Summary

Status: Decision Rendered

Appeal ID: 33422

Submission Date: 8/12/24 10:51 AM

Hearing Date: 8/21/24

Case #: B-001

Appeal Type: Building

Project Type: Commercial

Building/Business Name: Maitripa College / Tara School

Appeal Involves: occ Change from B to E

Proposed use: Daycare within existing College

Project Address: 1632 SE 11th Ave

Appellant Name: Nate Ember

LUR or Permit Application #: Permit 24-013420-CO

Stories: 2 Occupancy: B, E Construction Type: VB

Fire Sprinklers: Yes - full NFPA 13

Plans Examiner/Inspector: Chanel Horn

Plan Submitted Option: pdf   [File 1]

Payment Option: electronic

Appeal Information Sheet

Appeal item 1

Code Section

OSSC 1004.5 Areas Without Fixed Seating, Table 1004.5 Maximum Floor Area Allowances per Occupant

Requires

The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.5. For areas without fixed seating, the occupant load shall be not less than that number determined by dividing the floor area under consideration by the occupant load factor assigned to the function of the space as set forth in Table 1004.5. Where an intended function is not listed in Table 1004.5, the building official shall establish a function based on a listed function that most nearly resembles the intended function.
Exception: Where approved by the building official, the actual number of occupants for whom each occupied space, floor or building is designed, although less than those determined by calculation, shall be permitted to be used in the determination of the design occupant load.

Code Modification or Alternate Requested

To reduce the total building occupant load based on a reasonable understanding that some spaces within the building will only be used by occupants who move from one area (classroom space) to another (play area) such that these loads would not be simultaneous / cumulative.

Proposed Design

The proposed change of occupancy involves classroom space for daycare use; these spaces determine the total E occupant load. An existing warehouse space is proposed for indoor play space, and although the occupant load / density is considered in these spaces for the purposes of egress compliance, the occupant load in the play space are not cumulative in the overall building occupant load since the students who use it will be the same students who are already accounted for in the classroom calculations (excluded from simultaneous use). This is also consistent with state regulations for child care services through DELC.

Reason for alternative

This alternate is based on our understanding of a reasonable proposal to the building official per the code exception, consistent with historic approvals for similar circumstances. It enables reasonable use of an existing space for much-needed child care, and the resulting occupant loads align with the intended licensing capacity of 30 students.

Appeal Decision

Allow for a reduced occupant load due to non-simultaneous use: Denied. Proposal does not provide equivalent fire and life safety.

"PLEASE READ THE NOTE BELOW when providing Board requested Additional Information or when submitting a reconsideration after 1st time appeal Denial.

A reconsideration is submitted online following the same submittal process and using the same appeals form as the original appeal. Indicate at the beginning of the appeal form that you are filing a reconsideration and include the original assigned Appeal ID number. The reconsideration will receive a new appeal number.

Include the original attachments and appeal language. Provide new text with only that information that is specific to the reconsideration in a separate paragraph(s) clearly identified as ""Reconsideration Text"" with any new attachments also referenced. Once submitted, the appeal cannot be revised.

No additional fee is required when the Board has requested additional information or for the first reconsideration of a denied appeal if submitted within 6 months of the original appeal. In these two specific instances please ignore the auto-generated request for another fee.

PLEASE NOTE that there will be no auto-generated verification that the appeal is successfully submitted. To verify this by viewing the submitted appeal, go to;

https://www.portlandoregon.gov/bds/appeals/?action=search .

Then click on ""SEARCH"" and you will see the most recent 500 appeals in order that they have been filed. Find your appeal, click on ""view"" and then on ""file"". You can also refine the results by filling in a search word such as your name. Pursuant to City Code Chapter 24.10, you may appeal this decision to the Building Code Board of Appeal within 90 calendar days of the date this decision is published.  For information on the appeals process, go to www.portlandoregon.gov/bds/appealsinfo, call (503) 823-6251 or come to the Development Services Center."