Appeal 33431

Appeal Summary

Status: Hold for additional information

Appeal ID: 33431

Submission Date: 8/20/24 11:00 AM

Hearing Date: 8/28/24

Case #: B-002

Appeal Type: Building

Project Type: commercial

Building/Business Name: Pioneer Square Park / TriMet

Appeal Involves: Alteration of an existing structure

Proposed use: Existing TriMet TPSS electrical equipment room

Project Address: 701 SW 6th Ave

Appellant Name: Neil Lee

LUR or Permit Application #: Preliminary

Stories: 1 Occupancy: F1 Construction Type: 3B

Fire Sprinklers: No

Plans Examiner/Inspector: N/A

Plan Submitted Option: pdf   [File 1]   [File 2]

Payment Option: mail

Appeal Information Sheet

Appeal item 1

Code Section

OSSC Chapter 1010.1.1 Size of Doors.

Requires

The required capacity of each door opening shall be sufficient for the occupant load and provide a minimum clear opening width of 32 inches (813 mm). The clear opening width of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees (1.57 rad). Where this section requires a minimum clear opening width of 32 inches (813 mm) and a door opening includes two door leaves without a mullion, one leaf shall provide a minimum clear opening width of 32 inches (813 mm). In Group I-2, doors serving as means of egress doors where used to move beds shall provide a minimum clear opening width of 411/2 inches (1054 mm). The maximum width of a swinging door leaf shall be 48 inches (1219 mm) nominal. The minimum clear opening height of doors shall be not less than 80 inches (2032 mm), utilization of a full height door (6-8").

Code Modification or Alternate Requested

Access door height issue from electrical room.

Proposed Design

The proposed access door from the electrical room to the Bicycle storage room has approximately 24” difference in floor height. There is an unrelocatable Utility line restriction at the ceiling of the lower floor level at the opening, that will not allow a full height door. We are only able to create a 36” wide by 6’-3” high door

Reason for alternative

The existing physical structural and utility conditions prevent installing a full height door. Note the NEC requires a minimum door height of 6’-5” however, it is noted that the existing electrical room has an existing exit door of 7’-0” high, and a second existing large access hatch up a ladder to the sidewalk above the room.

Appeal Decision

Allow a 6'-3" high door to access an existing electrical room: Hold for additional information. Provide amperage of system in room and provide egress plan from electrical room. Appellant may contact Joe Botkin for more information #503-823-5915 Email: Joseph.Botkin@portlandoregon.gov

PLEASE READ THE NOTE BELOW when providing Board requested Additional Information or when submitting a reconsideration after 1st time appeal Denial.

A reconsideration is required for submission online following the same submittal process and using the same appeals form as the original appeal. Indicate at the beginning of the appeal form that you are filing a reconsideration and include the original assigned Appeal ID number. The reconsideration will receive a new appeal number.

Include the original attachments and appeal language. Provide new text with only that information that is specific to the reconsideration in a separate paragraph(s) clearly identified as ""Reconsideration Text"" with any new attachments also referenced. Once submitted, the appeal cannot be revised.

No additional fee is required when the Board has requested additional information or for the first reconsideration of a denied appeal if submitted within 6 months of the original appeal. In these two specific instances please ignore the auto-generated request for another fee.

PLEASE NOTE that there will be no auto-generated verification that the appeal is successfully submitted. To verify this by viewing the submitted appeal, go to;

https://www.portlandoregon.gov/bds/appeals/?action=search .

Then click on ""SEARCH"" and you will see the most recent 500 appeals in order that they have been filed. Find your appeal, click on ""view"" and then on ""file"". You can also refine the results by filling in a search word such as your name.