Appeal 33445
Appeal Summary
Status: Decision Rendered OVER 33419 FROM (8/14/24) for more info
Appeal ID: 33445
Submission Date: 8/29/24 8:23 AM
Hearing Date: 9/4/24
Case #: B-004
Appeal Type: Building
Project Type: commercial
Building/Business Name: Julia West
Appeal Involves: Reconsideration of appeal
Proposed use: Multi-Family Residential
Project Address: 522 SW 13th Ave
Appellant Name: Nici Stauffer
LUR or Permit Application #: Permit 23-052714- CO
Stories: 12 Occupancy: R-2 Construction Type: IVB
Fire Sprinklers: Yes - NFPA 13, throughout
Plans Examiner/Inspector: Maureen McCafferty
Plan Submitted Option: pdf [File 1] [File 2] [File 3]
Payment Option: electronic
Appeal Information Sheet
Appeal item 1
| Code Section | 2022 OSSC 602.4.2.5 Concealed spaces and 2022 OMSC 602.2.1 Materials within plenums |
|---|---|
| Requires | OSSC 602.4.2.5 states that concealed spaces in type IVB construction shall not contain combustibles other than electrical, mechanical, fire protection, or plumbing materials and equipment permitted in plenums in accordance with Section 602 of the Mechanical Code, and shall comply with all applicable provisions of Section 718. Combustible construction forming concealed spaces shall be protected in accordance with Section 602.4.1.2. OMSC602.2.1 states that except as required by Sections 602.2.1.1 through 6.2.2.1.8, materials within plenums shall be noncombustible or shall be listed and labeled as having a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with ASTM E84 or UL 723. The exceptions include the following:
5.1. Continuous non-combustible raceways or enclosures.
|
| Code Modification or Alternate Requested | The goal of this appeal is to clarify the intent of the OSSC and OMSC regarding type IVB buildings and concealed spaces and plenums and allow combustible MEP items to be in approved gypsum board assemblies and walls packed with non-combustible materials as is written in the mechanical code that is referenced. |
| Proposed Design | ORIGINAL TEXT The permitted type IVB building has mechanical, electrical and plumbing materials located in plenums and walls throughout the building. This appeal proposes that the intent of the OSSC and OMSC sections referenced allow for combustible MEP items in the below bullet pointed conditions, based on the associated listed exceptions in OMSC 602.2.1. • Combustible MEP materials within rated wall or ceiling assemblies (exception 5.2) The design includes firestopping at all MEP penetrations through rated floors, requiring tested firestopping systems with an F and T rating to match the assembly. Firestopping is also required at all penetrations through rated walls. At all other concealed locations, MEP materials will prescriptively meet the requirements of OMSC 602 as is referenced in OSSC 602.4.2.5, or be protected by an insulating wrap specific to the material and rated for use in plenums per exception 5.3. RECONSIDERATION TEXT The permitted type IVB building has mechanical, electrical and plumbing materials located in plenums and walls throughout the building. This appeal proposes that the intent of the OSSC and OMSC sections referenced allow for combustible MEP items in the below bullet pointed conditions, based on the associated listed exceptions in OMSC 602.2.1. • Combustible MEP materials within listed and rated gypsum board assemblies (Exception 5.2), see drawing exhibits. The design includes firestopping at all MEP penetrations through rated floors, requiring tested firestopping systems with an F and T rating to match the assembly. Firestopping is also required at all penetrations through rated walls. At all other concealed locations, MEP materials will prescriptively meet the requirements of OMSC 602 as is referenced in OSSC 602.4.2.5, or be protected by an insulation wrap specific to the materials and rated for use in plenums per exception 5.3. While the type IVB requirements for concealed spaces references the plenum specific section of the mechanical code, none of the concealed spaces for this project are being used as air plenums. |
| Reason for alternative | ORIGINAL TEXT The included drawing exhibits illustrate the fire ratings of all assemblies within the building and indicate firestopping at all MEP penetrations. 2-hour rated floor/ceiling assemblies (Reference A0.14) state that all mass timber elements exposed within a concealed space are covered by 80 minutes of type X gypsum board, as is required by OSSC 602.4.1.2. Where UL listed, fire rated demising walls (Reference A0.11) intersect with 2-hour rated horizontal assemblies, the underside of mass timber elements are covered by a minimum of 80 minutes of type x gypsum board (Reference A0.16), and walls are packed with fiberglass batt insulation to meet acoustic ratings and provide coverage of mass timber elements at the floor. Where unrated partition walls intersect with 2-hour rated horizontal assemblies, those containing combustible MEP items will be packed with mineral wool insulation (Reference A0.11). All MEP penetrations that occur through 2-hour rated floors are firestopped to prevent the passage of fire and smoke to other floors. Firestopping systems must be listed for use with the specified material and have F and T ratings equivalent to the rated assembly. We feel that this level of protection of mass timber elements, while isolating passage of fire and smoke between floors and protecting individual combustible MEP items with either mineral wool insulation or rated gypsum board assemblies, meets the intent of the code as it is written. In addition to our supporting drawings, a stamped letter from a licensed fire protection engineer is included to support this appeal. RECONSIDERATION TEXT OSSC 602.4.2.5, as prescriptively written, requires that OMSC 602.2.1 be referenced for all concealed spaces (not just plenums as the OMSC section describes) in type IVB construction. This mechanical code section requires that MEP materials be either noncombustible or be plenum rated and meet the requirements of ASTM E84 or UL 723, unless provisions of the listed exceptions are met. Exception 5.2 states that combustible MEP materials within approved gypsum board assemblies do not have to be tested in accordance with ASTM E84 or UL 723. Exception 5.3 states that combustible MEP materials that are fully enclosed within materials that are listed and labeled for installation within a plenum and listed for the application are acceptable. The mechanical code commentary further supports this interpretation, stating that “Exception 5 recognizes the practice of enclosing combustible materials, such as plastic piping, in gypsum board assemblies or in insulation materials that are listed and labelled for this specific application.” Within the permitted documents, wall and ceiling assemblies, both rated and unrated, encase combustible MEP materials. Where UL listed, fire rated walls occur in this project, they encase MEP materials within type X rated gypsum board that is fully taped and sealed to prevent the passage of fire. Walls are packed with either friction fit unfaced fiberglass batt insulation or cavity rock mineral wool, shown to have a fire and smoke developed index less than 25/50 per the testing requirements of ASTM E84. Per the written exceptions and further explanation in the code commentary, we can interpret that UL listed, fire rated assemblies are an example of ‘approved gypsum board assemblies.’ All penetrations through UL listed, fire rated, vertical assemblies are sealed for fire according to OSSC 714. All horizontal penetrations are sealed for fire per OSSC 714. Low voltage and electrical wiring with minimal amounts of PVC or similar insulation jackets (see materials exhibit) run through multiple areas of the building. All of these areas are to be packed with mineral wool or fiberglass batt insulation. All mass timber elements within concealed areas and walls are fully covered by 80 minutes of type X gypsum board per the requirements of the code. The included drawing exhibits illustrate the fire ratings of all assemblies within the building and indicate firestopping at all MEP penetrations. 2-hour rated floor/ceiling assemblies (Reference A0.14) state that all mass timber elements exposed within a concealed space are covered by 80 minutes of type X gypsum board, as is required by OSSC 602.4.1.2. Where listed, fire rated demising walls (Reference A0.11) intersect with 2-hour rated horizontal assemblies, the underside of mass timber elements are covered by a minimum of 80 minutes of type x gypsum board (Reference A0.16), and walls are packed with unfaced fiberglass batt insulation to meet acoustic ratings and provide coverage of mass timber elements at the floor. Unfaced fiberglass batt insulation meets the flame and smoke spread limits of ASTM E84 and is considered non-combustible per model building codes (see materials exhibit). Where unrated areas contain low volt or electrical wiring, cavities will be packed with unfaced fiberglass batt insulation or mineral wool insulation (Reference A0.11) and all mass timber elements will be covered per the requirements of the code with 80 minutes of type X gypsum board. All MEP penetrations that occur through 2-hour rated floors are firestopped to prevent the passage of fire and smoke to other floors. Firestopping systems must be listed for use with the specified material and have F and T ratings equivalent to the rated assembly. The specific MEP materials being used are included in the appeal exhibits. PVC vent piping, and low volt wiring with PVC or XLP insulating jackets are the items that do not outright meet the requirements for plenums. PVC does not support combustion. Should a fire event occur within the building, elements are protected at a minimum by 5/8” type X gypsum board, which prescriptively provides 40 minutes of protection. XLP insulating jackets are flame retardant and low smoke. We feel that this level of protection of mass timber elements, while isolating passage of fire and smoke between floors and protecting individual combustible MEP items within rated gypsum board assemblies or areas friction fit and fully packed with insulation materials with a flame and smoke spread index less than 25/50, meets the intent of the code as it is written. In addition to our drawings, and a spreadsheet of MEP materials with supporting cutsheets, a stamped letter from a licensed fire protection engineer is included to support this appeal. |
Appeal Decision
Allow combustible MEP components to be located in concealed spaces in Type IV-B construction: Granted as proposed for the products and conditions outlined.
"The Administrative Appeal Board finds that the information submitted by the appellant demonstrates that the approved modifications or alternate methods are consistent with the intent of the code; do not lessen health, safety, accessibility, life, fire safety or structural requirements; and that special conditions unique to this project make strict application of those code sections impractical.
Pursuant to City Code Chapter 24.10, you may appeal this decision to the Building Code Board of Appeal within 90 calendar days of the date this decision is published. For information on the appeals process, go to www.portlandoregon.gov/bds/appealsinfo, call (503) 823-6251 or come to the Development Services Center."