Appeal 33451
Appeal Summary
Status: APPROVED
Appeal ID: 33451
Submission Date: 9/2/24 3:53 PM
Hearing Date: 10/3/24
Case #: 24-64
Appeal Type: Fire
Project Type: residential
Building/Business Name:
Appeal Involves: Erection of a new structure
Proposed use: Residential
Project Address: 9245 E Burnside St
Appellant Name: Brian Fosse
LUR or Permit Application #: Permit 23-067064-000-00-RS
Stories: 1 Occupancy: R-3 Construction Type: Type V
Fire Sprinklers: No
Plans Examiner/Inspector: JOE THORNTON
Plan Submitted Option: pdf [File 1] [File 2]
Payment Option: electronic
Appeal Information Sheet
Appeal item 1
| Code Section | 507.5.1 |
|---|---|
| Requires | 507.5.1 requires all portions of Group R-3 structures to be no more than 600 feet from a hydrant along a fire apparatus road. |
| Code Modification or Alternate Requested | We request allowance for structures within the development to be up to 200 feet from the fire apparatus access road. The included plan shows that 2 units (O and P) do not meet the requirements of 503.1.1. |
| Proposed Design | The project will replace the existing 8-10 foot wide gravel/dirt public alleyway adjacent to the site with a 20 foot wide paved alley section providing fire access to the property. NFPA 13D sprinklers are proposed for units M, N, O, and P.” |
| Reason for alternative | The 20 foot wide paved public alley will provide adequate access to all of the proposed units on site. Additionally, units M, N, O, and P will have sprinkler systems installed. |
Appeal Decision
09.05.2024
Brian Fosse
920 NW Naito Pkwy, #J3
RE: 9245 E Burnside St
APPEAL ID #33451; Case #24-64
Dear Brian Fosse:
The Administrative staff has reviewed your appeal regarding 9245 E Burnside St. The Administrative staff has reviewed your appeals regarding the fire apparatus access road width and grade, the appeals are granted as proposed.
If you have any question regarding the appeal outcome or the Board of Appeal process, please call me at 823-3724.
Sincerely,
Kari Schimel, Fire Marshal
Appeal Board Coordinator
KS:ls