Appeal 33469
Appeal Summary
Status: DECISION RENDERED OVER 33441 FROM 9/4/24 FOR MORE INFO.
Appeal ID: 33469
Submission Date: 9/11/24 1:55 PM
Hearing Date: 9/18/24
Case #: B-004
Appeal Type: Building
Project Type: commercial
Building/Business Name: French International School of Oregon
Appeal Involves: Reconsideration of appeal
Proposed use: E-Occupancy, preschool/ school
Project Address: 8500 NW Johnson St.
Appellant Name: Peter Dixon
LUR or Permit Application #: Permit 24-035913 -CO
Stories: 2 Occupancy: E Construction Type: V-B (new), V-N (existing)
Fire Sprinklers: Yes - New - Fully Sprinklered
Plans Examiner/Inspector: John Cooley
Plan Submitted Option: pdf [File 1] [File 2] [File 3] [File 4]
Payment Option: electronic
Appeal Information Sheet
Appeal item 1
| Code Section | OSSC 2022 1009.1 Accessible Means of Egress |
|---|---|
| Requires | Where more than one means of egress is required by Section 1006.2 or 1006.3 from any accessible space, each accessible portion of the space shall be served by not less than two accessible means of egress. |
| Code Modification or Alternate Requested | Allow one accessible means of egress, where a single means of egress is permitted, where rooms exit directly to the exterior. |
| Proposed Design | See attached code plan (1/G-105). On the upper level, all classrooms have an exterior exit door, facing a mostly enclosed courtyard/ play area at grade. There are no interior exit corridors. Sectors F and H are provided with two accessible means of egress. One egress path is an accessible route at grade to the right-of-way. The other path uses an exterior exit stairway (per OSSC 1027), with an exterior area for assisted rescue (per OSSC 1009.7). At Sector I, one (1) accessible exit is provided. Two (2) total accessible exits are provided from the courtyard. One to the north, and another via the west stair. Reconsideration Text |
| Reason for alternative | Per 1006.3.4, a single exit is permitted from any story where: Reconsideration Text |
Appeal Decision
Arrangement of accessible means of egress: Granted provided no obstructions are placed in common area that would impede the accessible means of egress.
"The Administrative Appeal Board finds that the information submitted by the appellant demonstrates that the approved modifications or alternate methods are consistent with the intent of the code; do not lessen health, safety, accessibility, life, fire safety or structural requirements; and that special conditions unique to this project make strict application of those code sections impractical.
Pursuant to City Code Chapter 24.10, you may appeal this decision to the Building Code Board of Appeal within 90 calendar days of the date this decision is published. For information on the appeals process, go to www.portlandoregon.gov/bds/appealsinfo, call (503) 823-6251 or come to the Development Services Center."