Appeal 33476
Appeal Summary
Status: Decision Rendered
Appeal ID: 33476
Submission Date: 9/12/24 4:37 PM
Hearing Date: 9/25/24
Case #: B-003
Appeal Type: Building
Project Type: commercial
Building/Business Name: Albina One
Appeal Involves: Erection of a new structure
Proposed use: Apartments
Project Address: 1771 N Flint Ave
Appellant Name: Jeff Stern
LUR or Permit Application #: Permit 22-191430-CO
Stories: 7 Occupancy: R2 / B Construction Type: Type IIIA / Type IA
Fire Sprinklers: Yes -
Plans Examiner/Inspector: Anne Schmidt
Plan Submitted Option: pdf [File 1]
Payment Option: mail
Appeal Information Sheet
Appeal item 1
| Code Section | 2019 OSSC Section 1010.1.10 Panic and fire exit hardware |
|---|---|
| Requires | Swinging doors serving spaces with an occupant load of 50 or more in a Group A occupancy shall not be provided with a latch or lock other than panic hardware or fire exit hardware. The Playground + Patio (located in the North Courtyard) has a permitted occupancy of 91 per 1/G102. |
| Code Modification or Alternate Requested | This appeal is to allow the two exit doors from the Playground + Patio back into the building to have an approved locking device complying with the requirements of 2022 OSSC Section 1010.2.4.8 as outlined below in the Proposed Design. |
| Proposed Design | Per 2022 OSSC Section 1010.2.4.8:
8.1 Signage stating the maximum occupant load of 91 shall be permanently affixed on the interior side adjacent to each locked required exit access door serving the exterior area. |
| Reason for alternative | The Playground + Patio at the North Courtyard is intended for use by building occupants only and has both means of egress back into the interior of the building leading out to the main entrances and the public way. The requirement in the 2019 OSSC to have panic or fire exit hardware presents a significant security risk by potentially allowing uncontrolled free access into the building. The currently adopted 2022 edition of the OSSC provides a compliant pathway to address both security and egress requirements. Our proposed design fully complies with Section 1010.2.4.8 of the 2022 OSSC. |
Appeal Decision
Allow compliance with the 2022 OSSC section 1010.2.4.8 in lieu of 2019 OSSC section 1010.1.10 for panic and fire exit hardware for the Playground + Patio located in the North Courtyard: Granted as proposed.
The Administrative Appeal Board finds that the information submitted by the appellant demonstrates that the approved modifications or alternate methods are consistent with the intent of the code; do not lessen health, safety, accessibility, life, fire safety or structural requirements; and that special conditions unique to this project make strict application of those code sections impractical.
Pursuant to City Code Chapter 24.10, you may appeal this decision to the Building Code Board of Appeal within 90 calendar days of the date this decision is published. For information on the appeals process, go to www.portlandoregon.gov/bds/appealsinfo, call (503) 823-6251 or come to the Development Services Center.