Appeal 33545

Appeal Summary

Status: Decision Rendered - RECONSIDERATION OF 33475

Appeal ID: 33545

Submission Date: 10/24/24 2:16 PM

Hearing Date: 11/6/24

Case #: B-001

Appeal Type: Building

Project Type: residential

Building/Business Name: Argyle Apartments

Appeal Involves: Erection of a new structure,Reconsideration of appeal,other: item 2

Proposed use: Multi-family

Project Address: 1810 N Argyle Street

Appellant Name: Logan McClain

LUR or Permit Application #: Permit 22-181744-CO

Stories: 11 Occupancy: R2 Construction Type: IV-B

Fire Sprinklers: Yes - throughout

Plans Examiner/Inspector: Brian McCall

Plan Submitted Option: pdf   [File 1]   [File 2]

Payment Option: electronic

Appeal Information Sheet

Appeal item 1

Code Section

2902.1 Minimum Plumbing Fixtures

Requires

Plumbing fixtures shall be provided in the minimum number as shown in Table 2902.1 based on the actual use of the building or space. Uses not specifically listed in Table 2902.1 shall be considered individually by the building official and shall reflect the use of the space being served by the fixtures. This code shall determine the number of occupants.

Building Code sheet G0.04 calculations show that 297 water closets are required.

Code Modification or Alternate Requested

The building code calculations require 297 water closets and this appeal requests providing 295 water closets.

Proposed Design

The design proposes 295 water closets in 295 single-user toilet rooms.

Reason for alternative

The occupants of this R-2 dwelling unit and their guests all have access to single user toilet rooms in their residential units. Following the LS comments on 6/13/23, two single user toilet rooms were added to Floor Level 11 to serve roof deck amenity spaces. Additionally, one single user toilet room was added to Floor Level 1 for building leasing agents, their staff and the building maintenance personnel. The permit documents submitted on 9/1/2022 included two single user toilet rooms adjacent to the bike parking areas. Providing 295 of the required 297 plumbing fixtures meets the intent of the building code.

Appeal Decision

Allow five unisex restrooms, three on Level 1 and two on Level 11, to serve amenity spaces: Granted as proposed.

The Administrative Appeal Board finds that the information submitted by the appellant demonstrates that the approved modifications or alternate methods are consistent with the intent of the code; do not lessen health, safety, accessibility, life, fire safety or structural requirements; and that special conditions unique to this project make strict application of those code sections impractical.

Pursuant to City Code Chapter 24.10, you may appeal this decision to the Building Code Board of Appeal within 90 calendar days of the date this decision is published. For information on the appeals process, how to file a reconsideration, and appealing to the Building Code Board of Appeal, go to https://www.portland.gov/ppd/file-appeal/appeal-process or email PPDAppeals@portlandoregon.gov.