Appeal 33549
Appeal Summary
Status: APPROVED
Appeal ID: 33549
Submission Date: 10/28/24 6:36 PM
Hearing Date: 11/14/24
Case #: 24-80
Appeal Type: Fire
Project Type: lur
Building/Business Name: NEAGU-FOUR PLEXES
Appeal Involves: other: NEW 2 FOUR-PLEX
Proposed use: RESIDENTIAL
Project Address: 2135 SE 170TH AVE
Appellant Name: RICHARD S GEORGESCU P.E.
LUR or Permit Application #: Permit LU 24-060934 LPD
Stories: 2 Occupancy: RESIDENTIAL Construction Type: FRAMMING
Fire Sprinklers: Yes - 4 plexes
Plans Examiner/Inspector: Leah Dawkins
Plan Submitted Option: pdf [File 1]
Payment Option: electronic
Appeal Information Sheet
Appeal item 1
| Code Section | OFC 503.1.1 |
|---|---|
| Requires | The buildings has to be less than 150 ft from access rd., for not doing sprinklers. We have 300 ft. |
| Code Modification or Alternate Requested | We are asking to approve even is more with 50 feet. |
| Proposed Design | Between units will be retarded fire walls. |
| Reason for alternative | In terms to maximized the building area under Middle Housing. |
The administrative staff has not yet reviewed this appeal.