Appeal 33551
Appeal Summary
Status: CANCEL
Appeal ID: 33551
Submission Date: 10/29/24 1:16 PM
Hearing Date: 11/14/24
Case #: 24-79
Appeal Type: FIRE
Project Type: residential
Building/Business Name: DEKUM APARTMENTS
Appeal Involves: Erection of a new structure
Proposed use:
Project Address: 7013 NE 27TH AVE
Appellant Name: JUSTIN SMITH
LUR or Permit Application #: Permit 24-081693-FS
Stories: 3 Occupancy: R2 Construction Type: WOOD
Fire Sprinklers: Yes - 100%
Plans Examiner/Inspector: Joel Wilks
Plan Submitted Option: pdf [File 1]
Payment Option:
Appeal Information Sheet
Appeal item 1
| Code Section | 907.5.2.1.3.2 |
|---|---|
| Requires | in sleeping rooms of group r-1 and r-2 occupancies the audible smoke alarm in dwelling unit or sleeping unit shall be 520 hz signal complying with nfpa 72 |
| Code Modification or Alternate Requested | mirror the phase 1 building that was just completed 9 mo. ago building A and building B by installing the 120v smoke detectors in the units single station\multi station |
| Proposed Design | mirror the phase 1 building that was just completed 9 mo. ago building A and building B by installing the 120v smoke detectors in the units single station\multi station |
| Reason for alternative | circumstances are currently the electrical contractor that completed phase 1 installed 120v smokes and was approved so when they wired phase 2 the same and did not wire for system smoke detectors and the building is currently sheet rocked and painted |
Appeal Decision