Appeal 33564
Appeal Summary
Status: Decision Rendered - RECONSIDERATION OF 33538
Appeal ID: 33564
Submission Date: 10/30/24 10:12 PM
Hearing Date: 11/6/24
Case #: B-012
Appeal Type: Building
Project Type: commercial
Building/Business Name: Providence Park
Appeal Involves: Reconsideration of appeal
Proposed use: Sporting events and Concerts
Project Address: 1844 SW Morrison Street
Appellant Name: JOHN WEIL
LUR or Permit Application #: Permit 24-027519-CO
Stories: 4 Occupancy: A-5, A-3 Construction Type: II-A, I-B
Fire Sprinklers: Yes - throughout/ See G001
Plans Examiner/Inspector: Steve Mortenson
Plan Submitted Option: pdf [File 1] [File 2] [File 3]
Payment Option: electronic
Appeal Information Sheet
Appeal item 1
| Code Section | OSSC 2902.1 |
|---|---|
| Requires | OSSC 2902.1. Plumbing fixtures are required to be provided based on the total occupant load of the building. Portable plumbing fixtures are not specifically addressed in the OSSC or OPSC. |
| Code Modification or Alternate Requested | OSSC 2902.1. Provide portable plumbing fixtures for only the additional occupant load being added to the field during a Concert event. |
| Proposed Design | Apart from the increased occupant load proposed on the field during a concert, the occupant load of the building is not increasing as a result of this project. Refer to Sheet G004 for an occupant load comparison that shows an overall decrease in occupant load, when compared to the previous 2017 project (see Appendix A). Portable plumbing fixtures are proposed to be provided on the field for concert events, based on the increased occupant load. The existing projects show a total field occupant load of 5,000. This project proposes a maximum of 12,622 occupants on the field, which represents an increase of 7,622 occupants. Plumbing fixtures are not proposed to be provided for the existing occupants, as they are already provided with existing fixtures. Plumbing fixtures are proposed to be provided for the 7,622 added occupants. Due to the difficulty of providing permanent restroom facilities for the additional occupant load, and because the occupant load (and required fixture count) will vary for each event, portable facilities are proposed to be provided for each event. A sample layout of the portable facilities is shown on Sheet ES-101.C (see Appendix A). The layout is provided for informational purposes only, to demonstrate one option for locating the facilities. In this layout, single-user toilet rooms, hand washing stations, and drinking fountains are proposed. Section 213.2 of the 2010 ADA Standards mirrors the requirements of Section 1110 of OSSC, as seen in Figure 1 below. Figure 1: Comparison of ADA and OSSC Requirements Each have the same exception for reducing the percentage of required accessible toilet rooms from 100% to 50% when multiple single-user toilet rooms are provided in the same area of the building. However, this exception is referring to permanent facilities located in a building and is not necessarily envisioning outdoor events with temporarily elevated occupant loads. For this reason, the ADA includes an additional exception specifically for portable toilet units. This additional exception (Exception 3) allows only 5% of the portable toilet units to be accessible. The accessible portable toilet units provided for this project will be provided with the International Symbol of Accessibility (ISA) in accordance with ADA Section 703.7.2.1. Portable Toilet Units For the maximum permitted 12,622 occupants on the field: The above process will be followed for events with a field occupant load less than 12,622 and may results in fewer required fixtures. Portable Hand-washing Stations For the maximum permitted 12,622 occupants on the field: The above process will be followed for events with a field occupant load less than 12,622 and may results in fewer required fixtures. Portable Drinking Fountains
RECONSIDERATION TEXT
|
| Reason for alternative | The proposed design provides the code-required number of plumbing fixtures (water closets, lavatories, and drinking fountains) for the additional occupant load on the field. Since the code does not provide provisions for portable plumbing fixtures, this alternative design is proposed to allow these additional plumbing fixtures to be provided during a concert event. If permanent restroom facilities were to be required, the current infrastructure would not realistically be capable of providing new permanent facilities. Therefore, temporary facilities are proposed on the field. A benefit of this design is that the number and location of portable plumbing fixtures can be adjusted to match the field occupant load of each unique event. Additionally, this appeal requests to utilize the ADA requirement for number of accessible single-user restrooms, to align with other portions of the Stadium where a minimum of 5% of the water closets in multi-user restrooms are required to be accessible. If this alternative design was not proposed, then one-half of the portable restrooms would be required to be accessible. The proposed design is consistent with the Federal accessibility requirements of the 2010 ADA Standards and meets the intent of the code. |
Appeal item 2
| Code Section | OSSC 1110.2, Ex. 3. |
|---|---|
| Requires | OSSC 1110.2, Ex. 3. Where multiple single-user toilet rooms are clustered in a single location, at least 50% of the toilet rooms in the cluster are required to be accessible. |
| Code Modification or Alternate Requested | OSSC 1110.2, Ex. 3. Provide accessible toilet rooms such that a minimum of 5% of the toilet rooms will be accessible, as permitted by the 2010 Americans with Disabilities Act (ADA) Standards. |
| Proposed Design | Apart from the increased occupant load proposed on the field during a concert, the occupant load of the building is not increasing as a result of this project. Refer to Sheet G004 for an occupant load comparison that shows an overall decrease in occupant load, when compared to the previous 2017 project (see Appendix A). Portable plumbing fixtures are proposed to be provided on the field for concert events, based on the increased occupant load. The existing projects show a total field occupant load of 5,000. This project proposes a maximum of 12,622 occupants on the field, which represents an increase of 7,622 occupants. Plumbing fixtures are not proposed to be provided for the existing occupants, as they are already provided with existing fixtures. Plumbing fixtures are proposed to be provided for the 7,622 added occupants. Due to the difficulty of providing permanent restroom facilities for the additional occupant load, and because the occupant load (and required fixture count) will vary for each event, portable facilities are proposed to be provided for each event. A sample layout of the portable facilities is shown on Sheet ES-101.C (see Appendix A). The layout is provided for informational purposes only, to demonstrate one option for locating the facilities. In this layout, single-user toilet rooms, hand washing stations, and drinking fountains are proposed. Section 213.2 of the 2010 ADA Standards mirrors the requirements of Section 1110 of OSSC, as seen in Figure 1 below. Figure 1: Comparison of ADA and OSSC Requirements Portable Toilet Units For the maximum permitted 12,622 occupants on the field: The above process will be followed for events with a field occupant load less than 12,622 and may results in fewer required fixtures. Portable Hand-washing Stations For the maximum permitted 12,622 occupants on the field: The above process will be followed for events with a field occupant load less than 12,622 and may results in fewer required fixtures. Portable Drinking Fountains
RECONSIDERATION TEXT |
| Reason for alternative | The proposed design provides the code-required number of plumbing fixtures (water closets, lavatories, and drinking fountains) for the additional occupant load on the field. Since the code does not provide provisions for portable plumbing fixtures, this alternative design is proposed to allow these additional plumbing fixtures to be provided during a concert event. If permanent restroom facilities were to be required, the current infrastructure would not realistically be capable of providing new permanent facilities. Therefore, temporary facilities are proposed on the field. A benefit of this design is that the number and location of portable plumbing fixtures can be adjusted to match the field occupant load of each unique event. Additionally, this appeal requests to utilize the ADA requirement for number of accessible single-user restrooms, to align with other portions of the Stadium where a minimum of 5% of the water closets in multi-user restrooms are required to be accessible. If this alternative design was not proposed, then one-half of the portable restrooms would be required to be accessible. The proposed design is consistent with the Federal accessibility requirements of the 2010 ADA Standards and meets the intent of the code. |
Appeal Decision
1. Allow portable plumbing fixtures for the additional occupant load added to the field during concert events: Granted in Appeal 33538 1a.
2. Allow the calculation of accessible portable water closets to be 5% rather than 50%: Granted as proposed.
Please note: Final occupant loads to be determined per special event permits through the Portland Fire & Rescue.
The Administrative Appeal Board finds that the information submitted by the appellant demonstrates that the approved modifications or alternate methods are consistent with the intent of the code; do not lessen health, safety, accessibility, life, fire safety or structural requirements; and that special conditions unique to this project make strict application of those code sections impractical.