Appeal 33575
Appeal Summary
Status: Decision Rendered RECONSIDERATION OF 33515
Appeal ID: 33575
Submission Date: 11/7/24 12:07 PM
Hearing Date: 11/13/24
Case #: R-001
Appeal Type: Building
Project Type: Residential
Building/Business Name:
Appeal Involves: Reconsideration of appeal
Proposed use: Garage / ADU
Appeal Information Sheet
Appeal item 1
| Code Section | R 105.1 and R 109.4 |
|---|---|
| Requires | This is a reconsideration of a previous appeal. that requested GPR testing and Photos R105.1 Required. R109.4 Approval required. |
| Code Modification or Alternate Requested | Approval of work completed on the foundation based on the submitted set that commenced prior to the issuance of the permit following the inspection of the form work and rebar by the engineer of record. |
| Proposed Design | Photo documentation of the construction as well as GPR data of the concrete post install indicating proper location of rebar. |
| Reason for alternative | The project was a fire damage repair with additional work, being a loss the owners insurance carrier was driving a schedule based on how long they would pay for the owners to live outside of the home. The intent was to expedite the work as long as we had approval from the engineer of record that the work was done per plans. We had the engineer do an inspection and there were no changes from the submitted foundation to the approved foundation plan. |
Appeal Decision
Request to approve the on-site inspection report by the Engineer of Record for foundation walls and footings instead of inspections by City Field Inspection staff: Granted as proposed.
"The Administrative Appeal Board finds that the information submitted by the appellant demonstrates that the approved modifications or alternate methods are consistent with the intent of the code; do not lessen health, safety, accessibility, life, fire safety or structural requirements; and that special conditions unique to this project make strict application of those code sections impractical.
"