Appeal 33605
Appeal Summary
Status: Decision Rendered
Appeal ID: 33605
Submission Date: 12/5/24 3:40 AM
Hearing Date: 12/11/24
Case #: B-009
Appeal Type: Building
Project Type: commercial
Building/Business Name: Pepsi B
Appeal Involves: Erection of a new structure
Proposed use: Residential Tower
Project Address: 830 NE 25th Ave
Appellant Name: Samir Mokashi
LUR or Permit Application #: Permit 24-039925-CO
Stories: 8 Occupancy: B, R2. A2, A3, M, R2, S1, S2 Construction Type: Type 1A and Type IIIB
Fire Sprinklers: Yes - Throughout
Plans Examiner/Inspector: Brian McCall
Plan Submitted Option: pdf [File 1]
Payment Option: electronic
Appeal Information Sheet
Appeal item 1
| Code Section | 403 - High Rise |
|---|---|
| Requires | 403.1 Applicability. High-rise buildings shall comply with Sections 403.2 through 403.6. |
| Code Modification or Alternate Requested | Request for relief from OSSC 403 high rise building provisions – except for fire pump, smoke detection, fire alarm, automatic sprinklers, manual wet standpipe in lieu of automatic standpipe, fire command room in lieu of a fire operations room, generator, exit stair separation, emergency escape, and elevator hoistway opening protection. |
| Proposed Design | The Pepsi B will be an 8-story apartment building with 5 stories of Type IIIA construction over 3 stories of Type IA construction. The two construction types are separated by a 3-hour horizontal fire rated assembly and protected throughout with an NFPA 13 automatic sprinkler system. While the top occupied story of the building will be located less than 75 feet above the lowest level of fire department access, the building will have an occupied roof deck, which will be located 8 feet above this height. The occupied roof area will be for the private use of owners, residents and guests only, with no access to the general public. The proposed design will mitigate the increased risk to occupants on this roof deck by including some high-rise building provisions that add value plus other fire and life safety provisions that provide direct relief to those on the terrace in an emergency. The intent is to be provide equivalent safety to the roof terrace occupants without burdening the project with cost that does not provide value to these small number of occupants or the rest of the building occupants. The key elements proposed are those that provide protected access to the emergency personnel and safe egress to the roof level occupants. This responds directly to the additional distance each group has to travel in an emergency. Additional measures increase the overall safety level for this building, even though it may not be directly related to the occupants on the roof. This will reduce the probability of a serious fire event at the roof level and make this design even more robust. A comparison against all of the high-rise provisions is included in the “reason for the alternative” section so that the appeal board can compare this proposal against a standard high-rise building. We are requesting relief from the following high-rise requirements: • SFRM bond strength of 430 psf. The proposal will meet the following high-rise requirements: The proposal will provide these additional measures to provide safer access and egress from the terrace: |
| Reason for alternative | With a height approximately 83 feet above the lowest level of fire department access, the occupied roof exceeds the high-rise threshold of 75 feet. The proposed design includes a base of Type I-A construction with 3-hour separation from the upper structure. The code does not provide a nuanced code path to the OSSC 403 high-rise requirements, so this appeal is for a customized approach based on compliance with many of the requirements, exceeding some, and requesting relief from others: • 403.1 Applicability – High-rise buildings shall comply with Sections 403.2 through 403.6. • 403.2 Construction – No reduction in fire resistance rating requested. Building exceeds. • 403.2.2 Seismic Considerations – All buildings fall under Category-II; no special requirements apply. Building complies. • 403.2.3 Structural Integrity of Interior Exit Stairways and Elevator Hoistway Enclosures – Not applicable. Building complies. • 403.2.4 Sprayed Fire-Resistant Materials (SFRM) – The bond strength of the SFRM installed throughout the building shall be in accordance with Table 403.2.4. Relief is requested from SFRM bond strength requirement of Table 403.2.4. • 403.3 Automatic Sprinkler System – Building will be fully sprinklered per Section 903.3.1.1. Building complies. • 403.3.3 Secondary Water Supply – A standpipe is provided at each of the stairs, and adequate water is available. Relief is requested from Section 403.3.3 for secondary water supply. • 403.3.4 Fire Pump Room – A fire pump is not required but is provided in a fire pump room separated from the rest of the building by a 2-hour fire barrier. Building exceeds. • 403.4.1 Smoke Detection – Provided throughout the building. Building complies. • 403.4.2 Fire Alarm System – Provided throughout the building. Building complies. • 403.4.3 Standpipe System – Provided throughout in all enclosed exit stairs of the building. Building complies. • 403.4.4 Emergency Voice/Alarm Communication System – Audio-visual fire alarm notification will be provided. Relief is requested from Emergency Voice/Alarm Communication System. • 403.4.5 Emergency Responder Radio Coverage – A Public Safety Distributed Antenna System (DAS) will provide enhanced two-way radio service, ensuring that first responders can maintain wireless communications within the building. Relief is requested from Emergency Responder Radio Coverage. • 403.4.6 Fire Command – The building will be provided with a Fire Operations Room, located near the west entrance, to allow the incident command officer to effectively manage resources. Relief is requested from Fire Command Center complying with Section 911. • 403.4.7 Smoke Removal – Relief is requested from smoke removal. • 403.4.8 Standby and Emergency Power – Emergency generator and tank is provided inside the building. The generator room is separated from the rest of the building by 2-hour fire barrier. Building exceeds. • 403.5.1 Remoteness of Interior Exit Stairways – Two exit stairs are located more than 30 feet apart. Additional exit stair is not required and not provided. Building complies. • 403.5.3 Stairway Door Operation – Stairway door unlocking to be provided at the enclosed stair extending to the occupied roof. Relief is requested from stairway door unlocking requirement for the second egress stair. • 403.5.3.1 Stairway Communication System – Stairway communication system is provided at the enclosed stair extending to the occupied roof. Relief is requested from stairway communication system for the second egress stair. • 403.5.4 Smokeproof Enclosures – Stair pressurization is provided at the enclosed stair extending to the occupied roof. The elevators are protected with a smokeproof lobby and smoke curtains on the hoistway enclosure. Relief is requested from smokeproof enclosures and shaft pressurization for the second exit stair. • 403.5.5 Luminous Egress Path Markings – Luminous egress markings are provided at the pressurized stair to the roof. Relief is requested from luminous egress markings for the second egress stair. • 403.5.6 Emergency Escape and Rescue – Emergency Escape & Rescue openings will be provided. Relief is requested from Emergency Escape and Rescue • 403.6 Elevators – Elevator hoistway door opening shall be protected per section 3006.3. Two-way communication is provided at elevators per section 3008.6.6. Building complies. • 403.6.1 Fire Service Access Elevator – Fire service access elevator is not required and not provided. Building complies. Equivalent and additional protection is provided by enhanced fire-resistive construction due to podium building and not taking advantage of available fire-resistive reductions. We are providing 2-hour protected stairs with a 3-hour base, standpipes provided in all stairs, fire pump provided and located in a room separated by a 2-hour fire barrier, smoke detection and fire alarm throughout the building, emergency responder radio coverage, emergency generator separated by 2-hour fire barrier, emergency escape and rescue openings, and smoke protection at elevator door openings. Additionally we are providing an enhanced means of egress corridor connecting the two exit stairs at the 8th floor as described in the proposed design section and including a 5 feet wide exit access stair from the roof level to the amenity room as shown on the attached plans. These additional mitigations, combined with the robust building construction as designed, provide protection and reduce the overall risk similar to a mid-rise building. Therefore, we urge you to approve this appeal. |
Appeal Decision
Omission of selected high-rise requirements for roof deck over 75 feet above the lowest level of fire department access: Hold for more information.
"Appellant has been sent an email clarifying the additional information requested. For information about how to file a reconsideration go to https://www.portland.gov/ppd/file-appeal/appeal-process or email PPDAppeals@portlandoregon.gov.
"