Appeal 33630

Appeal Summary

Status: APPROVED

Appeal ID: 33630

Submission Date: 12/20/24 3:43 PM

Hearing Date: 1/9/25

Case #: 25-03

Appeal Type: Fire

Project Type: commercial

Building/Business Name: Kiley40

Appeal Involves: Reconsideration of appeal

Proposed use: R2 apartment building

Project Address: 3950 N williams

Appellant Name: Bob Schatz

LUR or Permit Application #: Permit 24-029720-000- 00-CO

Stories: 5 Occupancy: R2 Construction Type: 3B

Fire Sprinklers: Yes - Whole building

Plans Examiner/Inspector: Steve Freeh

Plan Submitted Option: pdf   [File 1]

Payment Option: electronic

Appeal Information Sheet

Appeal item 1

Code Section

OFC 3303.1.1

Requires

Construction of 4 and 5-story wood framed structures to have an on-site security guard
during non-working construction times

Code Modification or Alternate Requested

The intent of this appeal is to provide onsite after hours security via a
dedicated camera surveillance system in conjunction with security response
protocol.

Proposed Design

Original text:
The proposed change is to have monitored Video Surveillance of the property during construction. The surveillance will begin once the second floor is framed and will be completed once the fire sprinkler system is complete and active. The surveillance company we plan on hiring is:
Advanced Locking Solutions
8300 SW Creekside place suite 150
Beaverton, OR 97008
https://www.advls.com/contact-us/
4 security cameras will be one the property, one in each corner. The system will be able to detect a breach of the premise as well as performing fire watch. Security will be in place until the project is complete and the fire protection system is fully charged and operational.
The site security and fire watch protocol will be as follows:
• The construction site perimeter is secured with lockable temporary fencing.
• Temporary doors and locks will be installed at all building entry points
asap.
• Cameras will be monitored during the non-work hours including:
Weekdays: 16:00 – 07:00. Weekends/holidays: 24 hours a day.
• Cameras will have back-up power.
• When there is intrusion at the site, the system has the ability to respond
with lights & strobes as well as communicating with the intruder via an
audio system. In the event of a site breach, the monitoring company will
contact the local Police Department to respond. The system has the ability
to detect flames and smoke. In the event of flame or smoke detection, the
monitoring company will call the local Fire Department to respond.
• If attempted entry by unauthorized personnel is discovered, security personnel
will call the appropriate law enforcement agency and remain on line until
they arrive.

Reconsideration text:
Security during non-working hours will be provided by a camera
surveillance system;
Advanced Locking Solutions
8300 SW Creekside place suite 150
Beaverton, OR 97008
https://www.advls.com/contact-us/
in conjunction with regular site visits by
DPI Security. Security cameras will be placed in the front and the back of the building to ensure
coverage of all buildings and fence entrances. The system will be able to
detect a breach of the premise as well as performing fire watch. Security
will be in place until the project is complete and the fire protection system
is fully charged and operational.
The site security and fire watch protocol will be as follows:
• The construction site perimeter is secured with lockable temporary
fencing.
• Temporary doors and locks will be installed at all building entry points
asap.
• Advanced Locking Solutions cameras will monitor for fire and intruders during non-work
hours.
• Cameras will be monitored during the non-work hours including:
Weekdays: 16:00 – 07:00. Weekends/holidays: 24 hours a day.
• Cameras will have back-up power.
• When there is intrusion at the site, the system has the ability to respond
with lights & strobes as well as communicating with the intruder via an
audio system. In the event of a site breach, the monitoring company will
contact the local Police Department to respond. The system has the ability
to detect flames and smoke. In the event of flame or smoke detection, the
monitoring company will call the local Fire Department to respond.
• Physical site monitoring/Fire Watch patrols will be performed by DPI
Security.
• DPI Security will perform (3) patrols per night, 7 days per week.
Along with the three (3) patrols per night on normal business days, there
will also be no less than six (6) visits per day on weekends and holidays.
These patrols will be no less than three (3) during the day, between 6 am
and 6 pm, and three (3) in the evening, between 6 pm and 6 am
• Additional response patrols will be available 24 hours a day.
• If attempted entry by unauthorized personnel is discovered, patrol officers
will call the appropriate law enforcement agency and remain on site until
they arrive.

Reason for alternative

Original text:
Hiring on-site security is very expensive. We feel we can get the same protection, if not better, with Video Surveillance of the property. Our surveillance will be monitored by a professional surveillance company that will have access to on-site security when unwanted activity is noticed. Also this will aid in not only fire protection but in theft protection in the
evenings and during the day.

Reconsideration text:
The proposed alternative methods for after hours security will provide
more reliable, continuous monitoring of the jobsite. The camera
surveillance system will be constantly live-monitored during after hours by
personnel, and will allow for the entirety of the jobsite to be kept under
observation at one time which therefore reduces the potential of the
occurrence and spread of fires during construction.

The administrative staff has not yet reviewed this appeal.