Appeal 33645

Appeal Summary

Status: Decision Rendered

Appeal ID: 33645

Submission Date: 1/9/25 3:04 PM

Hearing Date: 1/15/25

Case #: R-003

Appeal Type: Building

Project Type: COMMERICAL

Building/Business Name: W+R Homeownership

Appeal Involves: Reconsideration of appeal

Proposed use: Residential

Project Address: N Knott and N Vancouver

Appellant Name: Jeff Stern

LUR or Permit Application #: LUR 24-073629- LU

Stories: 3 Occupancy: R-3 Construction Type: Type V-B

Fire Sprinklers: Yes - At Duplexes (4 units per building)

Plans Examiner/Inspector: Jason Buerkle

Plan Submitted Option: pdf   [File 1]

Payment Option: electronic

Appeal Information Sheet

Appeal item 1

Code Section

Code Guide 19:11 Townhouses

Requires

One or more townhouses in a townhouse structure may be constructed as an attached two-family dwelling where one of the two dwelling units within the townhouse conforms to the City of Portland’s requirements for Accessory Dwelling Units (ADUs).

Code Modification or Alternate Requested

In lieu of the allowed Townhouse with ADU configuration, this appeal requests to allow a two-family townhouse, with an “over / under” dwelling configuration, to be attached to an abutting townhome within a Townhouse Structure (defined in Building Code Guide 19:11 as a group of attached townhouses).

The proposed “over/under” two-family townhouse configuration meets all other requirements of Building Code Guide 19:11.

This appeal is for the “Vancouver Building” which proposes (2) two-family townhomes (one on each end of the Townhouse Structure).


Proposed Design

Each of the (2) two-family townhomes are designed in accordance with Building Code Guide 19:11. Each dwelling in the two-family townhomes will be separated from one another by tested and listed, 1-hour fire resistance rated horizontal and vertical assemblies.

Each of the (2) two-family townhomes are proposed to be separated from their abutting townhomes according to ORSC Figure R302.2.1(3).

NFPA 13-D fire sprinklers will be installed throughout the two-family townhouse units.

Reason for alternative

ADUs are not allowed in the CM3 zone. If this project were in a residential zone, an appeal would not be required.

Appeal item 2

Code Section

ORSC Section R302.4.1 (Through Penetrations).

Requires

Through penetrations in fire-resistance-rated exterior walls, privacy walls and individual or common townhouse separation walls are not permitted in townhouses.

Code Modification or Alternate Requested

This appeal requests to allow a communicating door, connecting two dwellings within a two-family townhouse.

This appeal is for the “Vancouver Building” which proposes (2) two-family townhomes (one on each end of the Townhouse Structure).

Proposed Design

The proposed door is to be 60-minute rated, self-closing, include smoke gasketing, and have a privacy hardware set.

The proposed door is not a required means of egress for either dwelling. Separate egress is provided from each dwelling unit.

NFPA 13-D fire sprinklers will be installed throughout the two-family townhouse.

Reason for alternative

ADUs are not allowed in the CM3 zone. As such an appeal was submitted to allow the proposed configuration as a two-family townhouse. The client desires flexibility in how the “over / under” two-family townhouse configured dwellings can be used; specifically, to allow the potential for an extended / multi-generational family to occupy the separate units and maintain direct connection.

Appeal Decision

"Item 1: Allow (2) of (10) townhouse dwellings to be reviewed as two-family dwellings while meeting the requirements of Building Code Guide 19-11: Granted as proposed.
Item 2: Allow rated penetration within the required, vertical, fire-resistance rated dwelling separation wall: Granted as proposed."

"The Administrative Appeal Board finds that the information submitted by the appellant demonstrates that the approved modifications or alternate methods are consistent with the intent of the code; do not lessen the health, safety, accessibility, life, fire safety or structural requirements; and that special conditions unique to this project make strict application of those code sections impractical.