Appeal 33657

Appeal Summary

Status: DECISION RENDERED

Appeal ID: 33657

Submission Date: 1/12/25 6:17 PM

Hearing Date: 1/22/25

Case #: R-001

Appeal Type: Building

Project Type: Residential

Building/Business Name: forristal adu

Appeal Involves: Erection of a new structure

Proposed use: ADU

Project Address: 7144 N. concord

Appellant Name: dave Spitzer

LUR or Permit Application #: Permit 24-100557-RS

Stories: 1 Occupancy: R3 Construction Type: VB

Fire Sprinklers: No

Plans Examiner/Inspector: Robert B.

Plan Submitted Option: pdf   [File 1]

Payment Option: electronic

Appeal Information Sheet

Appeal item 1

Code Section

table R302.1 - Exterior walls

Requires

Exterior walls shall be of one hour rated construction within 3' of a property line

Code Modification or Alternate Requested

We want to build an ADU 2'-2"+/- away from the existing garage. To do so both the garage AND ADU wall need to be 1 hour rated with no eaves, etc.

Proposed Design

This appeal is for the ADU (being permitted separately from the garage 1 hr wall) to allow (2) 5/8" type 'x' to installed at the inside face of the wall as well as the inside face of the roof rim joist - there is no eave and the building is slab on grade. This will allow us to provide fire protection similar to the garage and have the siding smooth where the gyp. sheating would not be needed.

Reason for alternative

With both the garage and ADU having modified 1 hour walls - we feel each structure is protected from the adjacent structure.

Appeal Decision

Request modified version of 1-hour fire-resistance rated walls: Granted as proposed.

"The Administrative Appeal Board finds that the information submitted by the appellant demonstrates that the approved modifications or alternate methods are consistent with the intent of the code; do not lessen the health, safety, accessibility, life, fire safety or structural requirements; and that special conditions unique to this project make strict application of those code sections impractical.