Appeal 33675
Appeal Summary
Status: DECISION RENDERED
Appeal ID: 33675
Submission Date: 1/30/25 6:09 PM
Hearing Date: 2/5/25
Case #: B-003
Appeal Type: Building
Project Type: commercial
Building/Business Name: 9837 n lombard st
Appeal Involves: Alteration of an existing structure,occ Change from R3 to R2
Proposed use: apartments - low income housing
Project Address: 9837 n lombard st
Appellant Name: Dave Spitzer
LUR or Permit Application #: Preliminary
Stories: 2 Occupancy: R2 Construction Type: VB
Fire Sprinklers: Yes - Yes 13D in new apartment #3
Plans Examiner/Inspector:
Plan Submitted Option: pdf [File 1]
Payment Option: electronic
Appeal Information Sheet
Appeal item 1
| Code Section | 903.3.1.2 |
|---|---|
| Requires | Requires a NFPA 13R system in all residential buildings under the OSSC |
| Code Modification or Alternate Requested | We are asking for just the newly created unit to be sprinklered. |
| Proposed Design | The new unit would be the back 2/3rds of the ground floor of 9837 (unit #1) (9841 #2 is other side of duplex). We would like to install more robust sound and fire separations to compartmentalize our fire area. In exchange we would like to just sprinkle the newly created unit to NFPA 13D. |
| Reason for alternative | This additional unit would allow a second low income family to housed in these multi-bedroom houses. The costs of sprinklering the entire structure would make the project difficult financially. We believe that by increasing the fire and sound separation of all walls separating the new unit as well as the ceiling above the new unit we will provide equivalent protection while keeping the project affordable. |
Appeal item 2
| Code Section | TABLE 705.5 |
|---|---|
| Requires | REQUIRES walls less than 10' from the property line to be 1 hour fire rated |
| Code Modification or Alternate Requested | To allow the existing non-rated walls to remain as is. |
| Proposed Design | Our side yard setbacks are likely 5'. To retrofit the entire South and North exterior walls to 1 hr fire rating as well as the reduction in openings would be very difficult. We would be willing to install a sprinkler head over each window to provide equivalent protection. |
| Reason for alternative | The change of code from residential to commercial makes it difficult to impossible to add a unit to a duplex. In this case it would be under 800 sf - so could be considered an adu added to a duplex. We feel that sprinklering the new unit and above all exterior windows along the North and South walls will increase the safety of this building. |
Appeal Decision
ITEM 1: Allow 13D sprinkler system in one unit in lieu of 13R sprinkler system throughout: Denied. The proposal does not provide equivalent fire and life safety.
ITEM 2: Allow existing exterior walls to remain: Hold for more information.
"Pursuant to City Code Chapter 24.10, you may appeal this decision to the Building Code Board of Appeal within 90 calendar days of the date this decision is published. For information on the appeals process, how to file a reconsideration, and appealing to the Building Code Board of Appeal, go to https://www.portland.gov/ppd/file-appeal/appeal-process or email PPDAppeals@portlandoregon.gov.
"
"Appellant has been sent an email clarifying the additional information requested. For information about how to file a reconsideration go to https://www.portland.gov/ppd/file-appeal/appeal-process or email PPDAppeals@portlandoregon.gov.
"