Appeal 33684

Appeal Summary

Status: Decision Rendered

Appeal ID: 33684

Submission Date: 2/7/25 3:13 PM

Hearing Date: 2/19/25

Case #: P-001

Appeal Type: Building

Project Type: Residential

Building/Business Name:

Appeal Involves: Alteration of an existing structure

Proposed use: Not used.

Project Address: 1200 SW Boones Ferry RD

Appellant Name: Katherine Kallus

LUR or Permit Application #: Permit 24-081222 -SP

Stories: 2 Occupancy: Single family Construction Type: Log

Fire Sprinklers: No

Plans Examiner/Inspector: Lindsey Reschke

Plan Submitted Option: pdf   [File 1]

Payment Option: electronic

Appeal Information Sheet

Appeal item 1

Code Section

2023 OPSC 304.1

Requires

Section 304.1 of the 2023 Oregon Plumbing Specialty Code:

Plumbing fixtures, drains, appurtenances, and appliances, used to receive or discharge liquid wastes or sewage, shall be connected properly to the drainage system of the building or premises, in accordance with the requirements of this code.


340-071-0120(2)(b)

Each owner of real property is jointly and severally responsible for connecting all plumbing fixtures from which wastewater is or may be discharged to a sewerage facility or onsite system approved by DEQ or an agent.


340-071-0130(9)

All plumbing fixtures in dwellings, commercial facilities, and other structures from which sewage is or may be discharged must be connected to and discharge into an approved area-wide sewerage system or an approved onsite system that is not failing.


Code Modification or Alternate Requested

The log cabin was built in 1907 and is on the National Historic Registry, it would be ideal to cap the water and sewer line, disconnect fixtures in the home and place signs on them saying do not use, for historic representation only.

Proposed Design

We will cap the water and sewer line to the cabin, disconnect all internal fixtures, and sign them to say "Do not use, for historic representation only".

Reason for alternative

This alteration will allow the cabin to retain its historic value while still satisfying the City of Portland's requirement to disconnect the cabin's fixtures.

Appeal Decision

Granted provided permanent covers are installed on the fixtures to prevent debris from entering drains.

"The Administrative Appeal Board finds that the information submitted by the appellant demonstrates that the approved modifications or alternate methods are consistent with the intent of the code; do not lessen the health, safety, accessibility, life, fire safety or structural requirements; and that special conditions unique to this project make strict application of those code sections impractical.