Appeal 33703
Appeal Summary
Status: Decision Rendered - Reconsideration of 33687
Appeal ID: 33703
Submission Date: 2/20/25 10:47 AM
Hearing Date: 2/26/25
Case #: P-001
Appeal Type: Plumbing
Project Type: lur
Building/Business Name:
Appeal Involves: Reconsideration of appeal
Proposed use: Residential
Project Address: 8530 NE Holladay St
Appellant Name: Rees Bettinger
LUR or Permit Application #: LUR 24-103864
Stories: 2 Occupancy: Group R Construction Type: 4 plex
Fire Sprinklers: No
Plans Examiner/Inspector: Clare Fuchs
Plan Submitted Option: pdf [File 1]
Payment Option: electronic
Appeal Information Sheet
Appeal item 1
| Code Section | BCG 03-11: Private Plumbing Easements |
|---|---|
| Requires | III. Other Allowances and Restrictions. E. Eaves and other projections are allowed to project up to a maximum of 3 feet into a private plumbing line easement if all parts of the eave/projection are 15 feet or more above grade within the easement area. |
| Code Modification or Alternate Requested | I Have a Plan under construction with Porch roofs on the east side of the building that extend 2 feet into the 6 foot Utility easement. |
| Proposed Design | I Am not asking for an alternative method of construction of the sewer service but am asking that the hight restriction for the porches be lowered to 10 ft instead of 15ft or higher from Grade. The reason why it seams this is a legitimate appeal request is we are already restricting the method of maintenance and repair of the said sewer lines to Non open trench methods due to the easement being only 6 ft in width, Therefore alternative methods that do not require tall equipment will be used anyway based on the city's required maintenance Agreement Documents that must be recorded with these New Land division Plats. So the alternative is to record this Document with the restriction of Open trench Maintenance and repairs. "Reconsideration Text" Maximum Depth of the Sanitary Sewer in the easement Area is 40 inches Deep. |
| Reason for alternative | Because the Maintenance Agreement Prohibits open trench excavation anyway, And therefor alternative methods of maintenance and repair will be needed anyway , it seams that the risk of the porch overhangs being in the way of future maintenance and repair will not be an issue due to no open trench being allowed in the easement area. The Accessibility is not affected by the porches hight but equivalent accessibility is met though method restriction by way of Maintenance agreement "Reconsideration Text" The Depth of the sewer line for unit 4 as it enters the easement area is 20 inches deep. At the Front of the Lot at its deepest point All 4 sewer lines are 40 inches deep below grade. |
Appeal Decision
Reduction of easement height to 10 feet: Granted as proposed.
The Administrative Appeal Board finds that the information submitted by the appellant demonstrates that the approved modifications or alternate methods are consistent with the intent of the code; do not lessen the health, safety, accessibility, life, fire safety or structural requirements; and that special conditions unique to this project make strict application of those code sections impractical.