Appeal 33710

Appeal Summary

Status: Hold for Additional Information - Reconsideration of 33702

Appeal ID: 33710

Submission Date: 2/27/25 8:51 AM

Hearing Date: 3/5/25

Case #: B-004

Appeal Type: Building

Project Type: commercial

Building/Business Name: Veterans Memorial Coliseum

Appeal Involves: Alteration of an existing structure,Reconsideration of appeal

Proposed use: Stadium

Project Address: 300 N Ramsay Way

Appellant Name: Sara Ruzomberka

LUR or Permit Application #: Permit 25-010815 FA

Stories: 3 Occupancy: A4 Construction Type: Existing to Remain

Fire Sprinklers: Yes -

Plans Examiner/Inspector: Brian Quattlebaum

Plan Submitted Option: pdf   [File 1]   [File 2]   [File 3]

Payment Option: electronic

Appeal Information Sheet

Appeal item 1

Code Section

OSSC 903.2.1.3, OSSC 1030.6.2.3

Requires

Appeal Item 1 – Fire Sprinkler Elimination
OSSC 903.2.1.3. An automatic sprinkler system shall be provided throughout Group A-4 occupancies and throughout all stories from the Group A-4 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists: The fire area exceeds 12,000 SF, the fire area has an occupant load of 300 or more, the fire area is located on a floor other than a level of exit discharge serving such occupancies.
OSSC 1030.6.2.3 Enclose areas with walls and ceiling in buildings or structures containing smoke-protected assembly seating shall be protected with an approved automatic sprinkler system in accordance with 903.3.1.1. Exception, the floor area used for contests, performances, or entertainment provided that the roof construction is more than 50 feet above the floor level and the use is restricted to low fire hazard uses.

Code Modification or Alternate Requested

Appeal Item 1 - Fire Sprinkler Elimination To allow sprinklers to be omitted in the seating bowl while still classifying the building as fully sprinklered due to fire modeling. Reconsideration text: To allow sprinklers to be omitted from most of the Main Concourse due to fire modeling.

Proposed Design

Appeal Item 1 – Fire Sprinkler Elimination
See the sprinkler elimination report from FP&C Consultants dated February 24, 2023. Fire modeling was utilized to determine the automatic sprinkler system provided both over the seating area and the event floor would not activate during multiple fire scenarios.
Reconsideration text per Corey Stanley
Per our meeting on 3.14.2024 please see the information below regarding the fixed bowl seats
As requested below you will find specification information from the seating manufacturers regarding the 2 seats that are being considered for the VMC.
Irwin
Irwin will be able to document the following after the fabric is selected and certify the components in the seating meet the TB-117.
An example of the verbiage is as follows:
Irwin Seating Company certifies the fixed seating for this project complies and meets the TB117, component-based testing, including upholstery fabric and resilient cellular material (foam padding) used for this project as outlined in California Technical Bulletin No. 117 sponsored by the State of California Department of Consumer Affairs, Bureau of Home Furnishings and Thermal Insulation.
Hussey
Materials (Flammability) shall satisfy applicable test, codes, standards, or requirements as follows
a.Copolymer polypropylene shall have a burn rate of 1 inch (25.4mm) or less per ASTM 635
b.Upholstery materials shall meet requirements as set forth in the state of California Bureau of Home Furnishings Technical Bulletin 117
c.Fire-performance characteristics of Seat Padding: Provide seating that complies with test method: California Technical Bulletin 117
d.Cushioning and padding shall be self-extinguishing as defined in the requirements as set forth in State of California Bureau of Home Furnishings Technical Bulletin 117
Reconsideration text: See the sprinkler elimination report from FP&C Consultants dated February 18, 2025. Fire modeling was utilized to determine the automatic sprinkler system provided both over most of the Main Concourse would not activate.

Reason for alternative

Appeal Item 1 - Fire Sprinkler Elimination
Sprinklers are requested to be omitted inside the Seating Bowl. Due to the height, activation of these sprinklers is unlikely in the event of a fire. Fire modeling has been performed to demonstrate this.
Reconsideration text: Sprinklers are requested to be omitted for most of the Main Concourse. Due to the height, activation of these sprinklers is unlikely in the event of a fire. Fire modeling has been performed to demonstrate this. Only the portion of the Main Concourse with displays (as shown in the FP&C Consultants report dated February 27, 2025) will be sprinklered.

Appeal Decision

"Omission of sprinklers as listed in the report and smoke control alternative to include most of the Main Concourse:
Hold for Additional Information. Appellant may contact Corey Stanley (971 291-8919) Corey.Stanley@portlandoregon.gov with questions.

"Appellant has been sent an email clarifying the additional information requested. For information about how to file a reconsideration go to https://www.portland.gov/ppd/file-appeal/appeal-process or email PPDAppeals@portlandoregon.gov.
"