Appeal 33741
Appeal Summary
Status: Decision Rendered
Appeal ID: 33741
Submission Date: 3/24/25 12:40 PM
Hearing Date: 4/2/25
Case #: B-002
Appeal Type: Building
Project Type: commercial
Building/Business Name:
Appeal Involves: Erection of a new structure
Proposed use: Apartment
Project Address: 5981 SE 49th Ave
Appellant Name: Mike Perso
LUR or Permit Application #: Permit 24-062181-CO
Stories: 4 Occupancy: R-2 Construction Type: VA
Fire Sprinklers: Yes -
Plans Examiner/Inspector: John Cooley
Plan Submitted Option: pdf [File 1]
Payment Option: electronic
Appeal Information Sheet
Appeal item 1
| Code Section | Code Section: OSSC 1028.2 |
|---|---|
| Requires | Oregon Structural Specialty Code, 1028.2 Exit Discharge. |
| Code Modification or Alternate Requested | To provide equal and/or better egress route than code requires with current configuration from the stair exit access to the exit discharge. |
| Proposed Design | The Stair 1 interior exit access egresses through the lobby and discharges on the same level to an exterior door. This path is unobstructed and circulates away from architectural barriers and visibly connects to the main building entrance. It will take occupants 3 steps from the exit access door to reach sightline A. Reference Exhibit A. Exit signage shall be installed providing readily visible and identifiable direction at the exit path leading to the exit discharge. This exit route will be used primarily by occupants familiar and without special knowledge of the building. |
| Reason for alternative | The Stair 1 interior exit must egress at the southern end of the stair enclosure to maintain stair head height clearance and continuity. Architectural barriers at the lobby delineates a circulation path to and from the Building’s exit discharge. Alternative locations for the interior exit from Stair 1 would not provide a safer path due to fire separation at adjacent lots, obstructions of furniture, and architectural barriers. |
Appeal Decision
"Exit stair discharge with lobby exit not readily visible from point of termination of the enclosure: Denied. Proposal does not provide equivalent fire and life safety.
Appellant may contact John Cooley (503-865-6533) with questions."
"Pursuant to City Code Chapter 24.10, you may appeal this decision to the Building Code Board of Appeal within 90 calendar days of the date this decision is published. For information on the appeals process, how to file a reconsideration, and appealing to the Building Code Board of Appeal, go to https://www.portland.gov/ppd/file-appeal/appeal-process or email PPDAppeals@portlandoregon.gov.
"