Appeal 33753
Appeal Summary
Status: APPROVED
Appeal ID: 33753
Submission Date: 4/3/25 9:38 AM
Hearing Date: 4/17/25
Case #: 25-12
Appeal Type: Fire
Project Type: commercial
Building/Business Name: Port of Portland
Appeal Involves: Addition to an existing structure,Correction of a violation
Proposed use: Security Fencing
Project Address: 7201 North Marine Drive
Appellant Name: Gabe Villanueva
LUR or Permit Application #: Preliminary
Stories: 0 Occupancy: 0 Construction Type: Pedestrian Gates
Fire Sprinklers: No
Plans Examiner/Inspector: Gabe Villanueva
Plan Submitted Option: pdf [File 1]
Payment Option: electronic
Appeal Information Sheet
Appeal item 1
| Code Section | 33 CFR 126.5 (b) NFPA 307 (1995) |
|---|---|
| Requires | There shall be provided on marine terminal property, a sufficient number of accessible hydrants. The number and location of hydrants and hose connections shall be determined by the authority having jurisdiction, but shall not be spaced further apart than 300 ft. nor more than 150 ft. from a dead end area. |
| Code Modification or Alternate Requested | We now have direct access to public hydrants along N Marine Dr. adjacent to the marine property in question. |
| Proposed Design | Pedestrian gates were installed along our security fence line along N Marine Dr. allowing for direct access to public hydrants. |
| Reason for alternative | Public hydrants are now easily accessible from within the terminal property in question. |
The administrative staff has not yet reviewed this appeal.