Appeal 34798
Appeal Summary
Status: APPROVED
Appeal ID: 34798
Submission Date: 5/7/25 4:18 PM
Hearing Date: 5/15/25
Case #: 25-19
Appeal Type: Fire
Project Type: commercial
Building/Business Name: Lloyd Concert Venue
Appeal Involves: Addition to an existing structure
Proposed use: Concert Venue
Project Address: 901 NE Lloyd Center
Appellant Name: Boris Kratzenberg
LUR or Permit Application #: Permit 24-100604-000-00-CO
Stories: 2 Occupancy: A-1 Construction Type: IIIB
Fire Sprinklers: Yes - Throughout
Plans Examiner/Inspector: Brady Donahue
Plan Submitted Option: pdf [File 1]
Payment Option: electronic
Appeal Information Sheet
Appeal item 1
| Code Section | 2023 PFC 503.1.1 |
|---|---|
| Requires | Fire access roads shall extend to within 150 feet of all portions of the exterior walls of the first story of the |
| Code Modification or Alternate Requested | Portions of the East side of the building are 305ft distant from fire access through NE Multnomah Street. Alternate requested to provide exterior standpipe connection on Northeast corner stair in lieu of vehicular fire access across Plaza & between the building and existing mall structure. |
| Proposed Design | Architect is proposing to add a standpipe to the North-East Stair with an exterior hose connection. This allows for all exterior portions of the building to be accessible with a hose. |
| Reason for alternative | The project has undergone preliminary Fire Life Safety meetings. During these meetings, the Architect reviewed site conditions, including existing fire hydrant locations along 9th Avenue, the open Plaza at the corner of 9th and Multnomah, and future plans for the public right-of-way (NE 10th Avenue). |
The administrative staff has not yet reviewed this appeal.