Appeal 34831

Appeal Summary

Status: Decision Rendered

Appeal ID: 34831

Submission Date: 6/3/25 2:18 PM

Hearing Date: 6/11/25

Case #: B-1

Appeal Type: Building

Project Type: commercial

Building/Business Name: Our Just Future / PCC Southeast Multifamily Housing

Appeal Involves: Erection of a new structure

Proposed use: Multi Family Residential

Project Address: 7705 SE Division ST

Appellant Name: luke street

LUR or Permit Application #: Permit 24-040502 -CO

Stories: 4 Occupancy: R-2 Construction Type: V-A

Fire Sprinklers: Yes - Throughout

Plans Examiner/Inspector: John Cooley

Plan Submitted Option: pdf   [File 1]   [File 2]   [File 3]   [File 4]   [File 5]   [File 6]   [File 7]   [File 8]   [File 9]

Payment Option: electronic

Appeal Information Sheet

Appeal item 1

Code Section

703.2 Tested Assemblies

Requires

Configuration of the wide flange beams do not match the configuration of the the tested assemblies in the standard fireproofing section and Column Caps in intumescent fireproofing does match the configuration of the tested assemblies.

Code Modification or Alternate Requested

Proposed code modification is so we can use the attached Global Fire Protection Engineering Judgement thicknesses/backup to maintain the required fire rating.

Proposed Design

See attached Global Fire Protection Engineering Judgements for verification thicknesses used will maintain the required fire rating.

Reason for alternative

Lack of tested by all fireproofing manufacturers.

Appeal Decision

Alternate 1-hour fire protection of steel members with spray applied fire resistive material and intumescent coatings per engineered analysis: Granted as proposed.

The Administrative Appeal Board finds that the information submitted by the appellant demonstrates that the approved modifications or alternate methods are consistent with the intent of the code; do not lessen the health, safety, accessibility, life, fire safety or structural requirements; and that special conditions unique to this project make strict application of those code sections impractical.