Appeal 34949

Appeal Summary

Status: Decision Rendered

Appeal ID: 34949

Submission Date: 8/20/25 2:44 PM

Hearing Date: 8/27/25

Case #: B-3

Appeal Type: Building

Project Type: commercial

Building/Business Name: Pacwest Center

Appeal Involves: Erection of a new structure

Proposed use: Emergency Generator Room

Project Address: 1211 SW 5th Ave

Appellant Name: Phil Beatty

LUR or Permit Application #: Permit 25-064042-FA

Stories: 30 Occupancy: B Construction Type: 1

Fire Sprinklers: Yes - Level P1

Plans Examiner/Inspector: Brian Quattlebaum

Plan Submitted Option: pdf   [File 1]

Payment Option: electronic

Appeal Information Sheet

Appeal item 1

Code Section

BCG 99-10

Requires

Section II Specific Requirements, B. Location,1. Interior. Where installed inside a building, the equipment shall be located in an enclosure providing a two-hour occupancy separation from all other occupancies and uses, including mechanical equipment.

Code Modification or Alternate Requested

The intent is to get an approved alternative means and methods for BCG 99-10.

Proposed Design

We are proposing that we put fire sprinklers above the intake air grille on the outside of the north end of the new emergency generator room to provide fire protection in the event of a fire. The generator room will also have a new fire sprinkler system on the inside of the room.

Reason for alternative

The new emergency generator room is inside of the existing building envelope and requires a two-hour rated room per BCG 99-10. However, the room needs intake air even in the event of a fire for the generator to run and provide emergency power to the fire pumps. With the location of the new generator room on level P1, we are not able to duct intake air from outside into the new room.

Appeal Decision

Fire sprinkler protection of intake air grill in lieu of a fire damper: Denied. Proposal does not provide equivalent fire and life safety.
Appellant may contact Brian Quattlebaum (503 823-8131) with questions.

Pursuant to City Code Chapter 24.10, you may appeal this decision to the Building Code Board of Appeal within 90 calendar days of the date this decision is published. For information on the appeals process, how to file a reconsideration, and appealing to the Building Code Board of Appeal, go to https://www.portland.gov/ppd/file-appeal/appeal-process or email PPDAppeals@portlandoregon.gov.