Appeal 34991
Appeal Summary
Status: Decision Rendered- Reconsideration of Appeal 33751 (04.09.25)
Appeal ID: 34991
Submission Date: 10/2/25 9:52 AM
Hearing Date: 10/15/25
Case #: B-1
Appeal Type: Building
Project Type: commercial
Building/Business Name: Imago Theater
Appeal Involves: Reconsideration of appeal,other: adding stairlifts on the West Stairs, removing 2 sets of doors at these stairs
Proposed use: Theater
Project Address: 17 East 8th Ave
Appellant Name: Bruce Sternberg
LUR or Permit Application #: Other Preliminary
Stories: 2 Occupancy: A-3 Construction Type: III-N
Fire Sprinklers: Yes - Basement & First floor
Plans Examiner/Inspector: Geoffrey Harker
Plan Submitted Option: pdf [File 1] [File 2] [File 3]
Payment Option: electronic
Appeal Information Sheet
Appeal item 1
| Code Section | 1005.3.1, OSSC 7.16 |
|---|---|
| Requires | 1005.3.1-Exit width in inches shall be determined by multiplying the total occupant load served by the means of egress times .3 inches. Multiple means of egress shall be sized such that the loss of any one means of egress shall not reduce the available capacity to less than 50 per cent of the required capacity. The maximum capacity required from any story of a building shall be maintained to the termination of the means of egress. |
| Code Modification or Alternate Requested | To allow stairlifts, whose railings @ floor level reduce the required exit stair widths in certain stair runs in the West Stair and to allow that exit stair to be without rated fire doors swinging in the direction of travel.. |
| Proposed Design | Original appeal text - (excerpt is as follows)"The chairlift is our last resort and a crucial improvement which would give the staff and artist of Imago access to work spaces on the second floor. The intent is give our senior volunteers, employees and contracted workers who have difficulty climbng stairs a viable means of access to the second floor......" |
| Reason for alternative | Reconsideration Text - The alternative is required to expand handicapped accessibility to this important cultural facility for volunteers and the public |
Appeal Decision
Allow the installation of a chair lift to provide an accessible route to existing second floor workspaces: Denied. Proposal does not provide equivalent fire and life safety.
Appellant may contact Sarah Daley (971-438-7938) with questions.
Pursuant to City Code Chapter 24.10, you may appeal this decision to the Building Code Board of Appeal within 90 calendar days of the date this decision is published. For information on the appeals process, how to file a reconsideration, and appealing to the Building Code Board of Appeal, go to https://www.portland.gov/ppd/file-appeal/appeal-process or email PPDAppeals@portlandoregon.gov.