Appeal 35012
Appeal Summary
Status: Pending - Hold for more information
Appeal ID: 35012
Submission Date: 10/16/25 2:56 PM
Hearing Date: 10/29/25
Case #: B-2
Appeal Type: Building
Project Type: commercial
Building/Business Name: Goat Blocks
Appeal Involves: other: Locking Egress Door
Proposed use: Retail/Residential
Project Address: 975 SE 11th Ave
Appellant Name: John Burgard
LUR or Permit Application #: Preliminary
Stories: 6 Occupancy: 1 Construction Type: 2
Fire Sprinklers: Yes - Riser room
Plans Examiner/Inspector: Preliminary
Plan Submitted Option: pdf [File 1]
Payment Option: electronic
Appeal Information Sheet
Appeal item 1
| Code Section | 1010.2 / OSSC 1010.2.13 |
|---|---|
| Requires | "Door Operation" Except as specifically permitted by this section, Egress doors shall readily openable from the egress side without the use of a key or special knowledge or effort. |
| Code Modification or Alternate Requested | |
| Proposed Design | We will use a fail safe solenoid to lock the sliding auto doors, Install a emergency door release pull station with a tamper cover and signage above that reads " For emergency door release use pull station below". This Fail Safe Solenoid will be tied to the buildings Fire Alarm so that any general alarm will release the door so that it operates to its intended operation as a egress door. We will also have a access control card reader that will release the door for regular entry into the staircase or access to the elevator to exit staircase of the building. |
| Reason for alternative | |
Appeal Decision
Use of emergency door release to provide delayed egress at sliding doors into lobby from parking garage: Hold for more information.