Appeal 35017

Appeal Summary

Status: Decision Rendered- Reconsideration of Appeal 34976 (09.24.25)

Appeal ID: 35017

Submission Date: 10/22/25 4:59 PM

Hearing Date: 10/29/25

Case #: B-4

Appeal Type: Building

Project Type: commercial

Building/Business Name: James Beard Public Market

Appeal Involves: Alteration of an existing structure,Reconsideration of appeal

Proposed use: Retail

Project Address: 610 & 622 SW Alder

Appellant Name: Maureen Hardy

LUR or Permit Application #: Permit 25-039717-CO

Stories: 3 Occupancy: M, A-2, S Construction Type: III-B

Fire Sprinklers: Yes - Throughout

Plans Examiner/Inspector: John Cooley

Plan Submitted Option: pdf   [File 1]   [File 2]

Payment Option: electronic

Appeal Information Sheet

Appeal item 1

Code Section

2022 OSSC §404.5 Smoke Control – Atriums

Requires

A smoke control system shall be installed in accordance with §909.

Exceptions:

  1. In other than Group I-2, and Group I-1, Condition 2, smoke control is not required for atriums that connect only two stories.
  2. A smoke control system is not required for atriums connecting more than two stories when all of the following are met:

2.1 Only the two lowest stories shall be permitted to be open to the atrium.
2.2 All stories above the lowest two stories shall be separated from the atrium in accordance with the provisions for a shaft in §713.4.

Code Modification or Alternate Requested

RECONSIDERATION: The horizontal shutter is proposed to be located at the Ground Floor level, instead of the Level 1 level as previously approved in Appeal ID #34976. See revisions to stamped fire report (Rev01) attached.

Request to use a rated horizontal shutter to protect the atrium as a 2-story vertical opening.

Proposed Design

RECONSIDERATION: See new horizontal shutter location in the stamped Fire Report Rev01 attached.

ORIGINAL APPEAL (updated to match new shutter location):
The James Beard Public Marketplace will include a 3 story atrium connecting all three stories of the building (see Attachment A). The proposed design is to follow §404.5 Exception 1 which omits smoke control requirements for atriums connecting only two stories.

The atrium will be equivalent to a 2-story opening because it is separated from the Basement level by a 2-hr rated horizontal shutter. The horizontal shutter will be activated by the fire alarm to create a two-story opening with a single story above, preventing smoke migration to the third story. The shutter will be supported by 1-hour rated construction and additional sprinklers around the floor opening will protect the floor of the atrium after the shutter has closed. The remainder of the fixed floor will remain unrated as allowed for Type III-B construction.

Reason for alternative

RECONSIDERATION: See new horizontal shutter location in the stamped Fire Report Rev01 attached.

ORIGINAL APPEAL (updated to match new shutter location):
The building will include an atrium connecting all 3 stories of the market to allow daylight at all three stories via atrium skylights, to achieve a cohesive market presence between all 3 functional Market levels, and to meet energy conservation goals for reduced reliance on interior artificial lighting. Retrofitting a smoke control system into an existing building presents various technical challenges, including the difficulty in bringing sufficient make-up air to the lowest (basement) floor of the building. Instead, the proposed design is to protect the space as a two-story atrium during a fire event.

ACTIVATION:
The shutter will be installed to activate upon sprinkler waterflow or manual pull station initiated anywhere in the building. The selected McKeon H200 Series shutter features a fail-safe automatic self-closing mechanism which does not require power operation to self-close. Per NFPA 80 §8.4.1.3.1, the average closing speed of horizontal sliding doors must be not less than 6 inches/sec, not including any initial delay time for panel alarm communication. The manufacturer’s representative estimated that the proposed size of shutters for this project will close within approximately 20 seconds after activation. This closing speed limits the amount of smoke that is able to migrate to Level 2 above, minimizing tenability concerns for egress to the enclosed exit stairs from Level 2.

FIRE RATING:
The selected shutter provides 2 hour rated fire protection and is smoke/draft labeled per UL 1784 (see Attachment B). The rating exceeds the requirements of floor construction in a Type III-B building (0-hour rated per Table 601), and exceeds the requirements of atrium enclosure (1 hour rated per §404.6).

In following OSSC §711.2.3 requirements for rated horizontal assemblies, the supporting construction of the rated shutters will be protected to afford a minimum 1 hour fire-resistance rating as required for atrium separation. The rated supporting construction will include the beams around the floor opening and supporting columns to the foundation.

LISTINGS:
The OSSC includes prescriptive provisions for the use of fire shutters as part of vertical and horizontal fire door assemblies, but does not include or preclude the use of shutters in other applications. When used for fire door assemblies, OSSC §716.2.1.2 requires vertical applications to be tested per UL 10B / NFPA 252 and §712.1.13.1 requires load-bearing horizontal applications to be tested per NFPA 288. In this case, the opening is not an occupiable area and is surrounded by guardrails. Therefore, as a non-load bearing application, the shutter will meet equivalent test listings to UL 10B / NFPA 252. The shutter will be installed per NFPA 80 in accordance with §716.1.

OTHER VERTICAL OPENING:
The 3-story unenclosed stairway will be protected prescriptively as an exit access stairway using OSSC §1019 Exception 4, with sprinklered draft curtains. The stairway is not used as a required means of egress. Because the opening is protected as an exit access stair, using the prescriptive code exception provided as equivalent protection to rated enclosure, the stair opening is not considered an atrium and has protections in place to prevent migration of smoke and toxic gases to other stories.

CONCLUSION:
The proposed design provides equivalent or greater fire/life safety protection to the prescriptive code requirements of §404.5. Though the shutter does require time for activation, this is similar to the activation time of a smoke control system installed in a 3-story atrium. When closed, the shutter provides greater fire separation protection than the baseline requirement of a non-rated floor per §404.5 Exception 1 and Table 601.

Therefore, we request that the proposed protection using a rated horizontal shutter be permitted to protect the atrium.

Appeal Decision

Use of rated horizontal shutters to create an atrium that connects only two stories: Granted provided the horizontal shutters protecting the vertical openings are capable of independent activation by each of the following: Sprinkler system waterflow switches, beam detection.

The Administrative Appeal Board finds with the conditions noted, that the information submitted by the appellant demonstrates that the approved modifications or alternate methods are consistent with the intent of the code; do not lessen the health, safety, accessibility, life, fire safety or structural requirements; and that special conditions unique to this project make strict application of those code sections impractical.

Under City Code Chapter 24.10, you may appeal this decision to the Building Code Board of Appeal within 90 calendar days of the date this decision is published. For information on the appeals process, how to file a reconsideration, and how to appeal to the Building Code Board of Appeal, go to https://www.portland.gov/ppd/file-appeal/appeal-process or email PPDAppeals@portlandoregon.gov.