Appeal 35053
Appeal Summary
Status: Decision Rendered - Building Code Board of Appeal
Appeal ID: 35053
Submission Date: 12/12/25 8:20 AM
Hearing Date: 12/10/25
Case #:
Appeal Type: Building
Project Type: commercial
Building/Business Name: Asylum
Appeal Involves: Alteration of an existing structure,Reconsideration of appeal
Proposed use: R1 Short term residency
Project Address: 1428 SE 19th Ave
Appellant Name: Bob Schatz
LUR or Permit Application #: Permit 25-056566-CO
Stories: 3 Occupancy: M,B,R1 & R2 Construction Type: VB
Fire Sprinklers: Yes - Whole building
Plans Examiner/Inspector: John Cooley
Plan Submitted Option: pdf [File 1]
Payment Option: electronic
Appeal Information Sheet
Appeal item 1
| Code Section | Table 1006.3.4(2) Stories with one exit or access to one exit |
|---|---|
| Requires | A first story above or below grade plane with an R-1 occupancy, a maximum occupant load of 10 per story, and a maximum exit access travel distance of 75 feet is permitted. A second story above grade plane with an R-1 occupancy is not permitted with one exit. |
| Code Modification or Alternate Requested | Approval to allow a second story above grade plane with an R-1 occupancy and one exit, provided that the occupancy load does not exceed 10 persons per story and the maximum exit access travel distance does not exceed 75 feet. |
| Proposed Design | The project involves the conversion of existing R-2 occupancies on the second and third stories of an existing three-story building to R-1 occupancies. Each floor will have a maximum of 10 occupants, with egress provided via a single exterior exit stairway. The building is of Type V-B construction and is equipped throughout with an NFPA 13 fire sprinkler system. |
| Reason for alternative | This existing building currently contains R-2 occupancies on portions of the second floor and the entirety of the third floor—both allowed under the current code. We believe that R-1 occupancies present the same, or lower, hazard risk as R-2 occupancies. |
Appeal Decision
The Building Code Board of Appeal met on December 10, 2025, and the following decision was reached:
R-1 occupancy on the second floor, third floor, and occupied roof with access to only one exit: Denied. Proposal does provide equivalent fire and life safety.
Decision: Unanimous
Board Members: Eric Bressman, Beth Brett, and Sharon Nobbe
According to Oregon Revised Statutes 455.690, you may appeal this decision to the appropriate State of Oregon advisory board within 30 calendar days of this decision being published. For information on the appeals process and costs, including forms, appeal fees, payment methods, and fee waivers, contact the Oregon Department of Consumer and Business Services, Building Codes Division.