Appeal 35075

Appeal Summary

Status: Decision Rendered - Reconsideration of 34969 (9/10/2025)

Appeal ID: 35075

Submission Date: 1/14/26 3:10 PM

Hearing Date: 1/21/26

Case #: B-4

Appeal Type: Building

Project Type: commercial

Building/Business Name: PHAME

Appeal Involves: other: Extension of temporary use, reduced occupant load for permitting

Proposed use: Group B Classroom (adult) and Exercise Room

Project Address: 2446 SE Ladd Ave.

Appellant Name: Jon Creighton

LUR or Permit Application #: Permit 25-092372-CO

Stories: 1 Occupancy: B Construction Type: VB

Fire Sprinklers: No

Plans Examiner/Inspector: John Cooley

Plan Submitted Option: pdf   [File 1]

Payment Option: electronic

Appeal Information Sheet

Appeal item 1

Code Section

108.1

Requires

The building official is authorized to issue a permit for temporary structures and temporary uses. Such permits shall be limited as to time of service, but shall not be permitted for more than 180 days. The building official is authorized to grant extensions for demonstrated cause.

Code Modification or Alternate Requested

PHAME Arts Academy is seeking an extension of permit for temporary use of an existing single-story office building which was granted by appeal 34969 decision.

Proposed Design

No building modifications are proposed. PHAME will continue to operate under appeal 34969 conditions 1 and 2 - The maximum occupant load of the Main Flex Space will be held at 49 occupants, and events with larger occupant loads will obtain approval with a Special Event Permit through the Fire Marshal's Office.

Reason for alternative

Further conditions on appeal 34969 decision include: Change of Use permit Approved to Issue by Feb. 17, 2026 and Under Inspection by Mar. 17, 2026. We are requesting an extension of both timelines.

During permit review for official Change of Use, City permit comments included requirement by Transportation to close an existing unused driveway to the north of the intersection of SE 20th Ave and SE Division St. This will need to be done under a separate Minor Improvement Permit (MIP). We are currently working to include that scope of work documentation with our forthcoming permit comment responses with a target submission date by January 30th. However, Approval of the Change of Use building permit will not be granted until the MIP to close the driveway is also approved. This will likely extend Approved to Issue date beyond February 17th.

Additionally, work permitted under the MIP must have an approved final inspection by PBOT prior to the final building permit inspection by BDS. PHAME will need to hire a contractor for the right-of-way work, potentially raise funds to pay for it, and schedule completion of the work around their class schedule. This will inevitably push the Under Inspection date well beyond March 17th.

Appeal item 2

Code Section

1004.5 Exception

Requires

Per 1004.5, for areas without fixed seating, the occupant load shall be not less than that number determined by dividing the floor area under consideration by the occupant load factor assigned to the function of the space as set forth in Table 1004.5 [. . .] Exception: Where approved by the building official, the actual number of occupants for whom each occupied space, floor or building is designed, although less than those determined by calculation, shall be permitted to be used in the determination of the design occupant load.

Code Modification or Alternate Requested

We are seeking approval by the building official for a proposed occupant load that is less than that determined by calculation.

Proposed Design

We propose to cap the maximum occupant load of the Main Flex Space at 49 occupants to obtain Change of Use building permit for new tenant - PHAME Arts Academy. PHAME will limit the enrollment to not more than 45 students for their classes in this space, accounting for up to 4 instructors to be present. Refer to the attached drawing.

Reason for alternative

Per previous appeal 34969, PHAME was granted temporary change of use for the building under conditions including capping the maximum occupant load of the Main Flex Space at 49 occupants. Calculated occupant load of that space is 103 occupants, which is more than can be accommodated by existing egress patterns. That would also result in a total building occupant load of 188, which is more than can be supported by the current plumbing fixture count.

Due to these complications, our Change of Use permit submission proposed a reduced occupant load for Main Flex Space. City permit review comments indicate this requires a building code appeal.

Appeal Decision

Item 1: Temporary use of office space for adult training from 9.18.25 to 5.21.26 while building permit is in process: Granted provided:
1. The maximum occupant load of the Main Flex Space is 49 occupants.
2. Events with larger occupant loads must be approved with a Special Event Permit through the Fire Marshal’s Office.
3. The building permit to change the use of the space is Under Review by Nov. 17, 2025.
4. The building permit to change the use of the space is Approved to Issue by Apr. 21, 2026.
5. The building permit to change the use of the space is Under Inspection by May 21, 2026.
Item 2: Reduce occupant load to 49 based on enrollment and instructor count: Denied. Proposal does not provide equivalent fire and life safety.
Appellant may contact Sarah Daley (971-438-7938) for more information.

The Administrative Appeal Board finds with the conditions noted, that the information submitted by the appellant demonstrates that the approved modifications or alternate methods are consistent with the intent of the code; do not lessen the health, safety, accessibility, life, fire safety or structural requirements; and that special conditions unique to this project make strict application of those code sections impractical.

Under City Code Chapter 24.10, you may appeal this decision to the Building Code Board of Appeal within 90 calendar days of the date this decision is published. For information on the appeals process, how to file a reconsideration, and how to appeal to the Building Code Board of Appeal, go to https://www.portland.gov/ppd/file-appeal/appeal-process or email PPDAppeals@portlandoregon.gov.