Appeal 35090
Appeal Summary
Status: Pending
Appeal ID: 35090
Submission Date: 1/28/26 6:19 PM
Hearing Date: 2/4/26
Case #: B-4
Appeal Type: Building
Project Type: commercial
Building/Business Name: NAYA Early Learning Center
Appeal Involves: Erection of a new structure
Proposed use: Daycare (TI Space)
Project Address: 5600 NE 42nd Ave.
Appellant Name: John Haswell
LUR or Permit Application #: Permit 22-127450-REV-07-CO
Stories: 1 Occupancy: E Construction Type: V-B
Fire Sprinklers: Yes - Building A and B
Plans Examiner/Inspector: Robert Keal
Plan Submitted Option: pdf [File 1]
Payment Option: electronic
Appeal Information Sheet
Appeal item 1
| Code Section | 2022 OSSC 503.1.2, 705.3 and Table 705.5 |
|---|---|
| Requires | 503.1.2 Buildings on same lot. Two or more buildings on the same lot shall be regulated as separate buildings or TABLE 705.5 |
| Code Modification or Alternate Requested | We ask to allow a canopy shade structure and storage box (Conex) to be located adjacent to each other in an outdoor |
| Proposed Design | An open (no exterior walls) steel framed canopy shade structure consisting of (4) steel posts and an upper roof section with metal frame and metal roof is to be placed within a metal fenced outdoor playground. We ask that an all metal storage container intended only for secure playground toy storage be allowed to be placed on a concrete slab adjacent to the canopy. There is an imaginary property line to the west of the storage box. Both sides of this imaginary property line have the same ownership and the line acts as a lease line between the parking lot for Portland Community College and the playground for the NAYA Early Learning Center. The adjacent use to the west of this line is zoning required loading zone parking. If for any reason future development to the west occurs, the storage container could be relocated if needed. The shade structure is located 10’ from the west imaginary property line and would not be required to be fire rated per section 705.5. |
| Reason for alternative | The shade structure is a completely open structural engineered metal structure anchored to concrete footings. It does not significantly limit movement of occupants of the playground in any direction. The structural metal frame is of non-combustible construction. All the structures are being added to the current building project and it does not appear that there is an ’existing building’ as specified in 705.3. The shade structure’s foundation has been installed as located in the 8/28/2023 Permit Rev #1 set which showed both the canopy and storage box. Based on the approved drawings and completed construction, there is nowhere to move the storage box that would not conflict with required fall zones for the installed playground equipment. It would create an undue hardship on the Early Learning Center Staff if the playground storage box must be removed. |
The administrative staff has not yet reviewed this appeal.