Appeal 8081
Appeal Summary
Status: Decision rendered
Appeal ID: 8081
Submission Date: 10/20/11 8:21 PM
Hearing Date: 10/26/11
Case #: B-010
Appeal Type: Building
Project Type: commercial
Building/Business Name: The Ocean, Building 2
Appeal Involves: Alteration of an existing structure
Proposed use: Mixed Use
Project Address: 511 NE 24th Ave
Appellant Name: Brett Schulz
LUR or Permit Application #: Permit 11-167343-CO
Stories: 1 Occupancy: F-2, R-3, B and/or M Construction Type: V-B
Fire Sprinklers: Yes - Residential unit only
Plans Examiner/Inspector: Peter Drake, Marcia Karr
Plan Submitted Option: pdf [File 1] [File 2] [File 3] [File 4] [File 5]
Payment Option: electronic
Appeal Information Sheet
Appeal item 1
| Code Section | OEESC 404.8 |
|---|---|
| Requires | OEESC 404.8 requires that exterior doors meet ASTM E 283 air leakage requirements. |
| Code Modification or Alternate Requested | |
| Proposed Design | Utilizing aluminum frame, double glazed overhead doors with weatherstripping, in three locations. Heat loss due to infiltration will be offset by using 97% efficient air-to-air heat pumps. |
| Reason for alternative | The overhead doors are an important part of the building design. It is not possible to meet prescriptive energy code with this type of door. It is anticipated that the 97% efficient heat pumps will exceed the heat loss from the overhead doors, providing a net gain in energy conservation. |
Appeal item 2
| Code Section | OSSC 903.2.8 |
|---|---|
| Requires | OSSC 903.2.8 requires an automatic sprinkler system be provided throughout all buildings with a Group R fire area. |
| Code Modification or Alternate Requested | |
| Proposed Design | Installation of 13R sprinkler system in residential unit only. A one hour rated partition will separate the residential unit from the commercial portion of the building. An additional layer of 5/8” gyp. board will be added to one side of the wall. |
| Reason for alternative | The one hour demising wall with additional layer of gyp. board will provide equivalent protection to a fully sprinklered building. |
Appeal item 3
| Code Section | Table 508.4 |
|---|---|
| Requires | Table 508.4 requires one hour occupancy separation between F-2 and R occupancies. |
| Code Modification or Alternate Requested | |
| Proposed Design | Provide one hour rated floor/ceiling between commercial bathrooms and sleeping lofts above, based on UL Design L507, with the following modifications: 1) Use 2x6 joists instead of 2x10. 2) Omit metal screening, 3) Use solid wood blocking instead of cross bridging, and 4) Use two layers of 5/8” gyp. board at ceiling instead of one ½” layer. |
| Reason for alternative | The revised design with additional layer of gyp. board will provide equivalent or better protection compared to the standard design. |
Appeal Decision
1. Air infiltration at overhead door: Denied. Proposal does not provide equivalent energy efficiency. Appellant may contact Marcia Karr (503-823-1107) for more information.
2. Fire sprinkler coverage: Denied. Proposal does not provide equivalent fire protection. Appellant may contact Peter Drake (503-823-7717) for more information.
3. Alternative fire-rated floor-ceiling assembly: Denied. Proposal does not provide equivalent fire resistance. It appears feasible to provide an approved assembly. Appellant may contact Peter Drake (503-823-7717) for more information.