Appeal 32353
Appeal Summary
Status: Decision Rendered
Appeal ID: 32353
Submission Date: 6/13/24 9:05 AM
Hearing Date: 6/20/24
Case #: B-008
Appeal Type: Building
Project Type: commercial
Building/Business Name: Hollywood Hub - BRIDGE Housing
Appeal Involves: Erection of a new structure
Proposed use: Residential
Project Address: 4160 NE Halsey St
Appellant Name: Lee Jorgensen
LUR or Permit Application #: LUR LU 23-004591 DZM
Stories: 12 Occupancy: A-3, B, R-2, S-1, S-2 Construction Type: 1A
Fire Sprinklers: Yes - Throughout
Plans Examiner/Inspector: John Cooley
Plan Submitted Option: pdf [File 1]
Payment Option: electronic
Appeal Information Sheet
Appeal item 1
| Code Section | OSSC Section 424.4 |
|---|---|
| Requires | OSSC 424.4 Separation. Play structures shall have horizontal separation from building walls, partitions, and from elements of the means of egress of not less than 5 feet. |
| Code Modification or Alternate Requested | The project proposes to construct an indoor play structure that is less than 5’ from building walls in limited areas in order to maximize caretaker visibility from adjacent spaces and maintain open space and access to the center of the room |
| Proposed Design | The designed play structure would meet all other requirements of Section 424 (Materials, Fire protection, Area limits). All surrounding building structure is non-combustible construction (gypsum board over metal studs and concrete), see Exhibit 1 for wall assembly construction. Increased fire sprinkler protection for room and wall-wash sprinkler heads at areas where separation is less than 5’ have been included in the design. See Exhibit #1 for plans showing areas of increased sprinkler protection, dimensions, and wall assemblies. |
| Reason for alternative | This affordable housing building is designed with families in mind, including amenity spaces for all ages. The urban context and site constraints require the kids’ play space to be located inside the building. We’ve designed it to take advantage of a double-height volume and direct adjacency to other building common areas. The dimensional constraints of the space require that elements of the play structure are located within 5’ of the perimeter walls of the room, in order to keep the central space open to allow the best sightlines and access for caretakers. The play structure is designed with minimal footprint touching the ground (maximizing circulation under and around the structure) and an adult “easy access” climbing stair to allow for caretakers, building staff, and first responders to enter the play structure as needed. Access in and out of the room, along the egress path, is unobstructed. The building is fully sprinklered, with an increase in coverage for this room that is 50% beyond code and additional wall-washing sprinkler heads located at the wall locations where the structure is less than 5’ from building walls. The proposed layout does an excellent job promoting safety and supervision within a fun, all-ages indoor play environment. |
Appeal Decision
Allow play structures with separation of less than 5' from building walls with increased fire sprinkler protection: Granted as proposed.
A separate permit from the Fire Marshal’s Office is required. Final sprinkler head location and coverage to be confirmed during fire permit review.
The Administrative Appeal Board finds that the information submitted by the appellant demonstrates that the approved modifications or alternate methods are consistent with the intent of the code; do not lessen health, safety, accessibility, life, fire safety or structural requirements; and that special conditions unique to this project make strict application of those code sections impractical.
Pursuant to City Code Chapter 24.10, you may appeal this decision to the Building Code Board of Appeal within 90 calendar days of the date this decision is published. For information on the appeals process, go to www.portlandoregon.gov/bds/appealsinfo, call (503) 823-6251 or come to the Development Services Center.